2.0 INSTALLATION
Wiring (continued)
For safety and to comply with regulations, battery over-current protection is required. Fuses and
disconnects must be sized to protect the wiring in the system and are required to open before the
wire reaches its maximum current carrying capability.
The National Electrical Code (NEC) requires both over-current protection and a disconnect
switch for residential and commercial electrical systems. These items are not supplied as part of the
inverter. However, Xantrex offers a DC rated, DC250/175 ETL listed, circuit breaker disconnect
module specifically designed for use with Trace™ inverters to meet NEC compliance. Two amperage
ratings are available: a DC250 (250 amps) and a DC175 (175 amps) in either single or dual breaker
configurations for single or dual inverter installations.
NOTE: Trace™ DC disconnects are not designed to accept doubled (paralleled) cables which may
be required for long cable runs. Also, the plastic red and black covers on the DC inverter inputs are
not designed to accommodate dual cables. If dual cables are used, the optional conduit box (DRCB)
must be used.
Some installations may not require conduit or a disconnect device, although over-current
protection is still required. Xantrex offers a fuse block (TFB) providing the code required inverter
over-current protection for these applications. Refer to the table below for the proper size disconnect
device for specific cable diameters.
Cable Size
Required
#2 AWG
#2/0 AWG
#4/0 AWG
NOTE: The NEC allows rounding to the next standard fuse size from the cable rating (i.e., 150 amp
cable size rounds up to a standard 175 amp size). The term “free air” is defined by the NEC as
cabling that is not enclosed in a conduit or a raceway. Cables enclosed in conduit or raceways have
substantially lower continuous current carrying ability due to heating factors.
Rating in
Maximum
Conduit
Breaker Size
115 amps max
N/A
175 amps max
DC175
250 amps max
DC250
Rating in "Free
Maximum Fuse
Air"
Size
170 amps max
TFB200
265 amps max
TFB300
360 amps max
TFB400