Powering Down The Inverter; Normal Operation; On Utility Power - MGE UPS Systems EXL 1000 User Manual

Hide thumbs Also See for EXL 1000:
Table of Contents

Advertisement

3.6
Powering down
the inverter
3.7

Normal Operation

Figure
I n d i c a t o rs d u r i n g n o r m a l o p e r a t i o n
3-13
"Load Protected" LED
Figure
D i a g r a m o f n o r m a l o p e r a t i o n o n u t i l i t y p o w e r
3-14
AC input
86-891000-00
The load is still supplied by AC input power via the "static bypass".
I
+ –
rectifier
charger
Installation and User's manual
Powering down the EXL 1000 for long periods is not
recommended because the battery should remain charged.
However, to carry out a power down, proceed as follows:
Shutdown the inverter (section 3.5)
Put the battery circuit breaker in the "off" position;
Turn off the input circuit breaker
All the LEDs on the control panel will go off.
WARNING
Put the upstream circuit breaker(s) on the low voltage
switchboard in "off" position.
The AC input power supply is present:
the green "load protected" light (figure 3-13) is on;
the power drawn by the load is supplied by AC input power
via the rectifier and inverter modules. The battery charger
float charges or recharges the battery.
voltage of the battery charger is temperature regulated to
ensure an optimal charge voltage.
O
inverter
battery
Operation
The DC output
load
3 — 7