4. Avoid locating multiple indoor units close to each other. This can result in crossing air patterns, uneven loads and
competing operation.
5. Do not install additional devices (such as smoke detectors) over the cabinet for facilitating routine maintenance.
Figure 2-6 indicates the installation location of the indoor unit.

2.4.3 Installation Procedure

1. Secure the mounting base made by yourself on the selected location. The outline and dimensions of the mounting
base are shown in Figure 2-7.
2. Lay a rubber cushion with 8mm ~ 10mm thickness on the mounting base, as shown in Figure 2-7.
3. Place the indoor unit onto the mounting base and secure it.
4. Rotate the grilles to regulate the airflow direction of the indoor unit, and the regulating angle is 45°, as shown in
Figure 2-8.
Figure 2-6 Installation location of the indoor unit
Rubber cushion
(8mm ~ 10mm thickness)
Rubber cushion
(8mm thickness)
Mounting base of DME07kW indoor unit
Rubber cushion
(8mm ~ 10mm thickness)
Rubber cushion
(8mm thickness)
Installation hole for
expansion bolt (M6 50)
Mounting base of DME12kW indoor unit
Figure 2-7 Mounting base (unit: mm)
New Liebert_DM Series Air Conditioner User Manual
Chapter 2 Mechanical Installation
Recommended
location
Not recommended location
510
Angle iron (30
square tube (25 25 3)
Steel plate (60 60 4)
600
Angle iron (30
square tube (25 25 2)
Steel plate (60 60 4)
×
×
30
×
3) or
×
×
×
×
×
30
×
3) or
×
×
×
×
9