Mechanical Parameters - Liebert DM Series User Manual

Hide thumbs Also See for DM Series:
Table of Contents

Advertisement

Chapter 2 Mechanical Installation
7

2.3.3 Mechanical Parameters

Indoor unit
The mechanical parameters of the indoor unit are shown in Figure 2-3 and Table 2-2.
1850
1750
600
510
510
600
DME07kW
DME12kW
Figure 2-3 Dimensions of indoor unit (unit: mm)
The shadows in Figure 2-3 indicate a reasonable installation and service space. The two sides of the unit need air
inlet. Enough service space must be reserved for the unit to facilitate maintenance.
The AC unit equipped with a heater should be kept a distance of minimum 150mm from combustible substance.
When testing the AC unit, keep the external static pressure below 150Pa lest the air volume becomes too low and the
heater becomes too hot.
Outdoor unit
The mechanical parameters of the outdoor unit are shown in Figure 2-4, Figure 2-5 and Table 2-2.
Figure 2-4 Dimensions of standard outdoor unit (unit: mm)
New Liebert_DM Series Air Conditioner User Manual