Set Points; System Status - Liebert DM Series User Manual

Hide thumbs Also See for DM Series:
Table of Contents

Advertisement

Settings
ENAB
DISA
OFF
Note
The alarms Hi Press, Lo Press and Hi Temp are serious fault alarms. So they cannot be set to OFF, but can only be set to
ENAB and DISA.
Customer Alarm
The AC unit provides two customer alarms, including customer 1 and customer 2, corresponding to PIN1, 2 of the
control terminals J19 and PIN5, 6 of J19 respectively.
The customer alarm can be set to 'NO' or 'NC'. You must set them according to the actual alarm signal of the control
terminals. If the power SPD is selected, the customer 1 alarm terminal has been connected with power SPD alarm
signal before delivery and the customer 1 has been set to 'NC'.

5.6.3 Set Points

Select Set Points in Main Menu to enter the Set Points menu, as shown in Figure 5-12.
The Set Points settings will not be lost when the power fails. For detailed setting ranges, refer to
Appendix 2 Parameter Setting Table.

5.6.4 System Status

Select Main Menu -> System Status to enter the System Status menu, as shown in Figure 5-13.
Analog
The Analog menu displays the indoor temperature & humidity, 3-ph voltage & frequency and condenser pressure with
a decimal in real time, as shown in Figure 5-14.
Ret Temp
Ret Hum
NTC0 Temp
Temp Calib
Time/Date
The Time/Date screen displays the current time and date of the system in the format of Year/Month/Date and
Hour/Minute/Second, as shown in Figure 5-15.
Table 5-4 Alarm output logic
Alarm history record
Alarm status record
Yes
Yes
No
Temp Stpt
Temp Sens
Hum Stpt
Hum Sens
Figure 5-12 Set Points menu
<Analog>
<Time/Date>
<In/Out Status>
<Run Time>
Figure 5-13 System Status screen
°
24.6 C
Hum Calib
67.8%
NTC0 Calib
°
25.0 C
Press 1:
15.6Bar
°
0.0 C
Press 2:
0.0Bar
Figure 5-14 Analog screen
New Liebert_DM Series Air Conditioner User Manual
Chapter 5 Micro-Processing Controller
Audible alarm
Yes
Yes
No
°
24.0 C
°
3.0 C
50.0%
5.0%
<Run Records>
0.0%
Phase A:
220.0V
°
0.0 C
Phase B:
220.0V
Phase C:
220.0V
Pwr Freq:
0.0Hz
Alarm prompt
Yes
Yes
No
No
No
No
Sw Code
0
31