Appendix 2 Parameter Setting Table

Menu
Alarm
Alarm Setpoint
Menu
Set Points
Analog
System
Status
In/Out Status
Setup System
System
Menu
Outdoor Unit
Select Options
Select
Options_CostSave
Mod_Economy Mod
Parameter
Hi Temp
Lo Temp
Hi Hum
Lo Hum
Air loss
Alarm output
(general alarm)
Alarm output
(serious alarm)
Customer 1
Customer 2
(remote shutdown)
TempStpt
TempSens
Hum Stpt
Hum Sens
Temp Calib
Hum Calib
NTC0 Calib
Manual Run Enab
In Fan Output
Comp Output
Heat Output
Hum Output
Low air Output
Out Fan Output
Mntr Addr
Mntr Prtcl
Baut Rate
Over Press
Under Press
Pwr Freq Devia
In Fan Start
In Fan Stop
Comp Run
Comp Stop
Cold St Delay
Hum Control
Temp Compsen
Factory Reset
Fan type
EC max. output
EC dehum output
Min. Volt
Max. Volt
Press BdWdth
Start Press
Heat
Hum
Economy Mod
Start At
End At
Zoom
New Liebert_DM Series Air Conditioner User Manual
Appendix 2 Parameter Setting Table
Default
35°C
15°C
65%RH
35%RH
25°C
ENAB
ENAB
NC (the unit equipped with
SPD is NC by default)
NC
24°C
3°C
50%RH
5%RH
0.0°C
0.0%
0.0°C
NO
OFF
OFF
OFF
OFF
OFF
OFF
1
YDN23
19200
15%
15%
3Hz
10s
30s
180s
180s
180s
RH
OFF
NO
AC
74%
60%
30%
100%
5Bar
13Bar
0
0
OFF
22:00
7:00
2°C
Setting range
25°C ~ 50°C
5°C ~ 20°C
65%RH ~ 90%RH
10%RH ~ 35%RH
30°C
OFF, ENAB, DISA
DISA, ENAB
NO, NC
NO, NC
15°C ~ 35°C
1°C ~ 5°C
20%RH ~ 80%RH
1%RH ~ 10%RH
-10°C ~ +10°C
-10% ~ +10%
-10°C ~ +10°C
YES, NO
ON, OFF
ON, OFF
ON, OFF
ON, OFF
ON, OFF
ON, OFF
1 ~ 254
YDN23, MODBUS
1200 ~ 19200
10% ~ 30%
10% ~ 30%
2Hz ~ 5Hz
10s ~ 600s
10s ~ 300s
60s ~ 300s
60s ~ 300s
30s ~ 240s
RH, AH
ON, OFF
YES, NO
AC, EC
50% ~ 100%
40% ~ 90%
30% ~ 50%
60% ~ 100%
4Bar ~ 6Bar
11Bar ~ 15Bar
0, 1
0, 1 (set Heat Num to 1 before setting
Hum Num to 1)
OFF, ON
18:00 ~ 3:00
5:00 ~ 10:00
2°C ~ 10°C
45