Liebert CRV+ Series Air Conditioner
User Manual
Version
V1.0
Revision date
November 11, 2013
BOM
31012977
Emerson Network Power provides customers with technical support. Users may contact
the nearest Emerson local sales office or service center.
Copyright © 2013 by Emerson Network Power Co., Ltd.
All rights reserved. The contents in this document are subject to change without notice.
Emerson Network Power Co., Ltd.
Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057, Shenzhen
China
Homepage: www.emersonnetworkpower.com.cn
E-mail: overseas.support@emerson.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CRV+ Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Liebert CRV+ Series

  • Page 1 Liebert CRV+ Series Air Conditioner User Manual Version V1.0 Revision date November 11, 2013 31012977 Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center. Copyright © 2013 by Emerson Network Power Co., Ltd.
  • Page 3: Table Of Contents

    Contents Chapter 1 Overview ................................1 1.1 Model Description ..............................1 1.2 Refrigerant Requirement ............................1 1.3 Product Introduction .............................. 2 1.4 Product Appearance ............................. 2 1.5 Main Components Of Indoor Unit.......................... 3 1.6 Environmental Requirements ..........................4 1.6.1 Operation Environment ..........................4 1.6.2 Storage Environment ..........................
  • Page 4 Chapter 4 System Power-On Commissioning ........................25 4.1 Location Of MCBs ............................... 25 4.2 Power-On Commissioning Of Air-Cooled Series Unit ..................25 4.2.1 Preparation Before Commissioning ......................25 4.2.2 Commissioning Procedures ........................26 4.2.3 Inspection After Commissioning ......................27 Chapter 5 Micro-Processing Controller ..........................28 5.1 Feature ................................
  • Page 5 Chapter 7 Troubleshooting ..............................49 Appendix 1 Circuit Diagram ............................... 53 Appendix 2 Menu Structure Of Micro-Processing Controller ..................... 55 Appendix 3 Alarm Control Menu Table..........................57 Appendix 4 Parameter Setting Table ..........................58...
  • Page 7: Chapter 1 Overview

    Chapter 1 Overview Chapter 1 Overview The Liebert CRV+ series precision air conditioner is a professional device, applicable to occasions inaccessible to general public. This chapter introduces the Liebert CRV+ series air conditioner on its model description, refrigerant requirement, product introduction, appearance, main components of indoor unit and requirements on operation and storage environment.
  • Page 8: Product Introduction

    DC speed regulation back-inclined centrifugal fan (EC fan for short). The Liebert CRV+ series air conditioner consists of an indoor unit and an outdoor unit. The Liebert CRV+ condenser is standard configuration, and it can reduce noise pollution to environment to greatest extent on the base of satisfying system cooling requirement, and improve reliability of operation.
  • Page 9: Main Components Of Indoor Unit

    Chapter 1 Overview 1.5 Main Components Of Indoor Unit The indoor unit of the Liebert CRV+ series air conditioner consists of DC brushless compressor, evaporator, electronic expansion valve, electrode humidifier, EC fan, electric heater, sight glass, filter dryer, micro-processing controller and so on.
  • Page 10: Environmental Requirements

    Chapter 1 Overview Remote Monitoring Software The Liebert CRV+ series air conditioner adopts Modbus protocol. Through the configured RS485 port or TCP/IP port, the Liebert CRV+ system can communicate with the host computer and receive the control of the host software.
  • Page 11: Chapter 2 Mechanical Installation

    The Liebert CRV+ series air conditioner is heavy (see Table 2-1 for the weight). It is recommended to use mechanical handbarrow such as an electric forklift to unload and move the equipment to the place closest to the installation site.
  • Page 12: Inspection

    1. The Liebert CRV+ series air conditioner is designed for split floor installation. The indoor unit must be installed on the floor of the equipment room or computer room, and the outdoor unit can be installed outdoors or on the floor of other rooms.
  • Page 13: System Installation Arrangement

    Chapter 2 Mechanical Installation 2.3 System Installation Arrangement 2.3.1 Overall System Arrangement The overall system arrangement of the Liebert CRV+ series air conditioner is shown in Figure 2-5. Condenser coil Evaporator coil Distributor Traps* (Every 7.5m of vertical lift) Sight glass...
  • Page 14: Mechanical Parameters

    Floor Heat insulation floor Outdoor unit Figure 2-7 Compressor installed higher than condenser 2.3.3 Mechanical Parameters Indoor unit The mechanical parameters of the indoor unit are shown in Figure 2-8 and Table 2-1. Liebert CRV+ Series Air Conditioner User Manual...
  • Page 15 C: Discharge pipe hole D: Cable entry hole E: Water inlet hole Figure 2-9 Locations of base plate pipe outlet Table 2-2 Locations and dimensions of base plate pipe outlet (unit: mm) Dimension Model CR025 CR035 Liebert CRV+ Series Air Conditioner User Manual...
  • Page 16 47.5 Front air outlet locations & dimensons The front air outlet locations & dimensions are shown in Figure 2-11. 1895 1895 CR035 CR025 Figure 2-11 Front air outlet locations & dimensions (unit: mm) Liebert CRV+ Series Air Conditioner User Manual...
  • Page 17: Installing Indoor Unit

    4. All the doors and windows should be closed and the openings should be as narrow as possible. Note The Liebert CRV+ series air conditioner is a professional device, and the indoor unit is prohibited to be used in an open atrocious outdoor environment.
  • Page 18: Installation Procedures

    Note: the space is used for regular maintenance, such as replacing filter, fan, electrode humidifier and so on 2.4.3 Installation Procedures The Liebert CRV+ air conditioner is used between racks, and at least one side of it is adjacent to server cabinet. Levelling the cabinet After all components of the cabinet have been installed, you need to level the cabinet.
  • Page 19 2. Use the provided M5 countersunk head screws to fix the cabinet connector in the installation holes on the cabinet frame, as shown in Figure 2-16. When connecting the racks without using the split plate, use the installation holes of the cabinet connector to connect the racks. Liebert CRV+ Series Air Conditioner User Manual...
  • Page 20: Piping

    T type three-way 0.21 0.10 0.76 0.24 0.12 0.76 0.27 0.15 0.76 0.18 0.76 0.44 0.24 1-1/8 0.56 Note A trap should be installed for every 7.5m of vertical distance. Please consult Emerson for details. Liebert CRV+ Series Air Conditioner User Manual...
  • Page 21 100kPa ~ 700kPa. Note Some product may contain components involved in local laws and regulations. Liebert CRV+ Series Air Conditioner User Manual...
  • Page 22 (under the raised floor included). Water inlet hole Drain hole Liquid pipe hole Discharge pipe hole Figure 2-19 Top pipe connectors Drain hole Liquid pipe hole Discharge pipe hole Cable entry hole Figure 2-20 Bottom pipe connectors Liebert CRV+ Series Air Conditioner User Manual...
  • Page 23: Charging Refrigerant And Adding Refrigerant Oil

    2.5.2 Charging Refrigerant And Adding Refrigerant Oil 1. Charging refrigerant The Liebert CRV+ series air conditioner has been charged in factory with 2bar nitrogen to keep the pressure. Table 2-8 and Table 2-9 give standard charging amount of outdoor unit (different models for different outdoor temperatures) and indoor unit condenser.
  • Page 24: Removing Transportation Fastener And Vibration Absorber

    Therefore, the refrigeration oil should be added. See the formula below: Amount of refrigeration oil (L) to be added = refrigerant refilling amount (kg) × 0.1 The refrigeration oil used in the Liebert CRV+ air conditioner are given in Table 2-12. Table 2-12 Types of refrigeration oil...
  • Page 25: Installation Inspection

    Adjusting wind-leading grill According to the installation location of the Liebert CRV+ air conditioner, you can adjust the installing direction of the wind-leading grill, making it lead wind to left or right. The wind-leading grill is composed of several pieces. Remove the screws on both sides of single piece of wind-leading grill, rotate it 180 degree, and install it back to change the wind direction.
  • Page 26: Chapter 3 Electrical Installation

    3.2.1 Electrical Port Location Of Indoor Unit For the Liebert CRV+ series unit, open the back door of indoor unit, you can see the specific layout and locations of low voltage components, as shown in Figure 3-1. For the detailed layout information of low voltage components, refer to the label pasted on the cabinet for distinguishing.
  • Page 27: Connecting Power Cable Of Indoor Unit

    Table 3-1 Full-load current (unit: A) Standard Standard model Standard model Standard model with electric Model model with electric heater with humidifier heater and humidifier CR025HA1380S02E10000PV000 24.86 24.86 CR025RA138SS12E10000PV000 CR035HA1380S02E10000PV000 31.6 46.6 42.3 46.6 CR035RA138SS12E10000PV000 46.6 Liebert CRV+ Series Air Conditioner User Manual...
  • Page 28: Connecting Control Cable

    3-4), each temperature sensor monitors the temperature of air entering each rack, and the read temperature value is used to control unit operation. The standard location of the sensor is 1.5m height. Therefore, the sensors should be placed on positions shown in Figure 3-4, or the devices cannot operate normally. Liebert CRV+ Series Air Conditioner User Manual...
  • Page 29: Connecting Solenoid Valve Of Pipe Extension Kit (Option For Site Installation)

    The solenoid valve of the pipe extension kit has two control cables, which are connected to the corresponding terminals on the control board. For the specific connecting ports on the interface board, refer to the connecting terminal number of liquid route solenoid valve in Appendix 1 Circuit Diagram. Liebert CRV+ Series Air Conditioner User Manual...
  • Page 30: Installation Inspection

    Table 3-1 for selecting apporopriate circuit breakers or fuses) The control connections are completed properly All wiring and connector connections are tight. The fixing bolts are tight After confirming the preceding points, you can start the commissioning operation. Liebert CRV+ Series Air Conditioner User Manual...
  • Page 31: Chapter 4 System Power-On Commissioning

    4.1 Location Of MCBs The MCB locations of Liebert CRV+ series unit are shown in Figure 4-1. For the MCB distribution in different unit electrical control box, please refer to the actual label on the cabinet for distinguishing.
  • Page 32: Commissioning Procedures

    When the compressor starts and operates, charge gas refrigerant (R410A) dynamically till there is no air bubble in the sight glass, the condensing subcooling degree reaches above 3K, and the suction overheating degree reaches above 7K. Liebert CRV+ Series Air Conditioner User Manual...
  • Page 33: Inspection After Commissioning

    Table 4-1 Inspection after commissioning Check item Result Check that all output functions are automatic Check that the temperature & humidity settings and control precisions are set reasonable Make sure all the other functions are set reasonable Liebert CRV+ Series Air Conditioner User Manual...
  • Page 34: Chapter 5 Micro-Processing Controller

    Chapter 5 Micro-Processing Controller This chapter gives a detailed description on feature, appearance, LCD screen, control buttons, control interface and menu structure of the micro-processing controller of the Liebert CRV+ series air conditioner. 5.1 Feature The micro-processing controller has the following features: 1.
  • Page 35: Control Button

    1. Press the Up or Down button to move the cursor on the Alarm Menu menu in the Main Menu screen. 2. Press the Enter button to enter the Alarm Menu menu. 3. Press the Up or Down button to move the cursor on Alarm Set in the Alarm Menu screen. Liebert CRV+ Series Air Conditioner User Manual...
  • Page 36: Control Screen

    Compressor capacity. Displaying the percentage of actual compressor capacity Heating state. Displaying 100% in heating mode, otherwise, displaying 0% Humidifying state. Displaying 100% in humidifying mode, otherwise, displaying 0% Dehumidifying state. Displaying 100% in dehumidifying mode, otherwise, displaying 0% Liebert CRV+ Series Air Conditioner User Manual...
  • Page 37: Password Screen

    Appendix 4 Parameter Setting Table. <Alarm Menu> <Temp&Hum Set> <System State> <System Set> Figure 5-7 Main Menu screen The menu items in the Main Menu screen are described in Table 5-4. Liebert CRV+ Series Air Conditioner User Manual...
  • Page 38: Alarm Menu

    Figure 5-10. XX is the serial number of the historical alarm record and YY is the total number of the historical alarm records. Figure 5-10 Alarm History screen Liebert CRV+ Series Air Conditioner User Manual...
  • Page 39 Alarm Stpt Select Alarm Stpt on the Alarm Set screen to enter the screen shown in Figure 5-13. Press the Up or Down button to scroll through the menus. Figure 5-13 Alarm Stpt menu Liebert CRV+ Series Air Conditioner User Manual...
  • Page 40 ENA and DISA. CP Driv Alarm Select CP Driv Alarm on the Alarm Set screen to enter the screen shown in Figure 5-16. Press the Up or Down button to scroll through the menus. Liebert CRV+ Series Air Conditioner User Manual...
  • Page 41: Temp&Hum Set

    Select Temp&Hum Set on Main Menu screen to enter the screen shown in Figure 5-19. The temperature & humidity settings will not be cleared upon system power-off. For the setting ranges of the settable menu items, refer to Appendix 4 Parameter Setting Table. Liebert CRV+ Series Air Conditioner User Manual...
  • Page 42: System State

    The Run State menu displays important operating parameters of devices, including ambient temperature & humidity, and the running states of compressor, fan and EEV, as shown in Figure 5-21. Figure 5-21 Run State menu Liebert CRV+ Series Air Conditioner User Manual...
  • Page 43 Select On/Off Record on System State screen to enter the screen shown in Figure 5-25. You can view the start and stop records of important components through this menu. the On/Off Record will not be cleared upon power-off. Liebert CRV+ Series Air Conditioner User Manual...
  • Page 44: System Set

    On the Common Set screen, press the Up or Down button to move the cursor to Rst Facty and press the Enter button, then press the Up or Down button to select YES or NO, and press the Enter button to confirm it. If YES is Liebert CRV+ Series Air Conditioner User Manual...
  • Page 45 Fan2 State will be displayed. Comp Set The Comp Set screen is shown in Figure 5-30. Figure 5-30 Comp Set menu EEV Set The EEV Set screen is shown in Figure 5-31. Figure 5-31 EEV Set menu Liebert CRV+ Series Air Conditioner User Manual...
  • Page 46: Help Menu

    Figure 5-34 Sel Option menu 5.6.6 Help Menu Select Help Menu on Main Menu screen to enter the screen shown in Figure 5-35. Enab 1st Run is not open to the user and cannot be viewed. Liebert CRV+ Series Air Conditioner User Manual...
  • Page 47: Display Set

    The Version Info menu is used to view the software version, as shown in Figure 5-38. Figure 5-38 Version Info menu 5.6.7 Display Set Select Display Set on Main Menu screen to enter the Display Set screen, as shown in Figure 5-39. Figure 5-39 Display Set screen Liebert CRV+ Series Air Conditioner User Manual...
  • Page 48: Chapter 6 System Operation And Maintenance

    Warning 1. During the operation of the Liebert CRV+ series air conditioner, lethal voltage may be present in the internal parts. It is a must to obey all the notes and warnings marked on the equipment or contained in this manual, otherwise injury or fatality may occur.
  • Page 49: Dust Filter

    Cut off the power before replacing the filter. Clear the fan operating time after replacing the filter. 6.3 Fan Kit EC fan The regular checking including motor operating status, fan impeller state, fan kit fixation and cooperation clearance between the fan and the wind-leading ring. Liebert CRV+ Series Air Conditioner User Manual...
  • Page 50: Electrode Humidifier

    The humidification control board is located in a metal box close to the humidifier and its interfaces are shown in Figure 6-3. Liebert CRV+ Series Air Conditioner User Manual...
  • Page 51 Reverse previous steps to re-assemble the humidifier, paying special attention to the following: 1. Protect the O-ring between the sealing canister bottom and the humidifier bracket. 2. Check and ensure that the steam outlet hose is connected without leakage. Liebert CRV+ Series Air Conditioner User Manual...
  • Page 52: Electrical Heater

    See Table 6-2 for details. Table 6-2 Discharge pressure System design kPa (PSIG) High pressure switch action point 3700 Liebert CRV+ Series Air Conditioner User Manual...
  • Page 53: Electronic Expansion Valve

    No direct contact between the refrigerant or lubricant and the skin when replacing the compressor, or serious burning or frostbite may occur. Put on gloves with long sleeves when processing polluted parts. The Liebert CRV+ system uses the DC brushless scroll compressor with high efficiency and high reliability. The engineering construction must be performed by following correct procedures strictly.
  • Page 54 If the valve is faulty, replace it too. Before the replacement, you must clean the system. If you are unsure about the cleaning method, please consult with Emerson service personnel. Liebert CRV+ Series Air Conditioner User Manual...
  • Page 55: Chapter 7 Troubleshooting

    L1, L2, L3 is normal heating is ineffective Cut off the power supply and measure the resistance of the heater Electric heater burned with an ohmmeter to judge if the heater is damaged Liebert CRV+ Series Air Conditioner User Manual...
  • Page 56 Check that the fans of the evaporator and condenser are normal over-temperature Regulate the electronic expansion valve or add proper Too high suction overheat degree amount of refrigerant Note: Judging the above symptoms is based on refrigerating command Liebert CRV+ Series Air Conditioner User Manual...
  • Page 57 ___ 4. Check the moisture content (through the sight glass) ___ 5. Check the electronic expansion valve Heating system ___ 1. Check the re-heater operation ___ 2. Check the erosion situation of the components Signature: _________________________________________________________ Note: copy this table for filing. Liebert CRV+ Series Air Conditioner User Manual...
  • Page 58 ___ 6. The temperature switch is set at the required position ___ 7. The refrigerant pipes are properly supported ___ 8. Check and fasten the circuit connections Signature _________________________________________________________ Note: copy this table for filing. Liebert CRV+ Series Air Conditioner User Manual...
  • Page 59: Appendix 1 Circuit Diagram

    Ethernet or CAN wiring BK-Black P-Purple Factory supplied 24 volt wiring BL-Blue R-Red Device own line BR-Brown YE-Yellow Inline quick disconnect WH-White GR-Grey Terminal block connector Y/GN-Yellow green Naked crimping connector Figure 1 CR025 circuit diagram Liebert CRV+ Series Air Conditioner User Manual...
  • Page 60 Ethernet or CAN wiring BK-Black P-Purple Factory supplied 24 volt wiring BL-Blue R-Red/ Device own line BR-Brown YE-Yellow Inline quick disconnect WH-White GR-Grey Terminal block connector Y/GN-Yellow green Naked crimping connector Figure 2 CR035 circuit diagram Liebert CRV+ Series Air Conditioner User Manual...
  • Page 61: Appendix 2 Menu Structure Of Micro-Processing Controller

    Appendix 2 Menu Structure Of Micro-Processing Controller Appendix 2 Menu Structure Of Micro-Processing Controller Figure 3 Menu structure of micro-processing controller Liebert CRV+ Series Air Conditioner User Manual...
  • Page 63: Appendix 3 Alarm Control Menu Table

    Tm Add Dup Com Fail of CP Driv Hi Exh Lock Ret Temp Sensor Alarm Driv Fail Lo Exh Lock Ret Hum Sensor Alarm Hi HS Temp Power Lost Air Temp Sensor Alarm Comp OC Liebert CRV+ Series Air Conditioner User Manual...
  • Page 64: Appendix 4 Parameter Setting Table

    ENA, OFF, DIS Alarm Ext Temp ENA, OFF Suc Temp ENA, OFF Ext Press ENA, OFF Suc Press ENA, OFF Com Fail ENA, OFF CP Driv Driv Fail ENA, OFF Alarm Comp OC ENA, OFF Liebert CRV+ Series Air Conditioner User Manual...
  • Page 65 NO, YES Rst Facty NO, YES Min Analog 0 ~ 30% Max Analog 100% 40 ~ 100% Fan Set Min Speed 30 ~ 50% Min CFC 0 ~ 30% Std Speed 75 ~ 100% Liebert CRV+ Series Air Conditioner User Manual...
  • Page 66 Heat Output OFF, ON Humd Output OFF, ON Pump Output OFF, ON Comm Alm OFF, ON Pump Conf No, YES Sel Option Rem Tem Num 0 ~ 10 Adj R.T1 0.0°C -10.0°C ~ 10.0°C Liebert CRV+ Series Air Conditioner User Manual...
  • Page 67 Menu Time (M) 0 ~ 59 Time (S) 0 ~ 59 Level One 1490 0000 ~ 9999 Password Level Two 0000 ~ 9999 Contrast 30 ~ 58 Display Set Language English Chinese, English Liebert CRV+ Series Air Conditioner User Manual...