Troubleshooting
HART Error Messages
Hart Application Error... "hc.ddl device revision x
not found."...Refresh System Card...See User's
Manual and Programming Interface for details.
Hart Application Error... "registry failure"...Reinstall
System Files...See User's Manual for details.
Voltage is currently detected at the Fieldbus
Terminals. Reconfigure unit and try again.
CDC Error..."failure while switching to
HART"...Reinstall System Files...See User's
Manual for details.
DD Error..."tokenizer mismatch"...DD version
<manufacture name, device name, dev. rev. #, and
DD rev. #>; HART application <version x.y>; HART
app version x.y...Reinstall DD...See Programming
Interface for details.
DD Error..."linker mismatch"...DD version x.y;
HART app version x.y...Reinstall DD...See
Programming Interface for details.
DD Error..."developed-to mismatch"...DD version
<manufacture name, device name, dev. rev. #, and
DD rev. #>; HART application <version x.y> ...See
Programming Interface for solution.
Warning: this DD is untested with the current Hart
App ver <manufacture name, device name, dev.
rev. #, and
DD rev. #>...you may experience unexpected or
inappropriate results...See Programming Interface
for details on DD updates...Do you want to accept
these risks and proceed?
DD Error..."tested-to sequence mismatch"...DD
version <manufacture name, device name, dev.
rev. #, and
DD rev. #>; HART application <version x.y>; HART
app version x.y...See Programming Interface for
solution.
DD Error..."developed-to mismatch"...DD version
<manufacture name, device name, dev. rev. #, and
DD rev. #>; HART application <version x.y>; HART
app version x.y...Reinstall DD...See Programming
Interface for details
DD Error..."DD header file corrupted"...Reinstall
Device version <manufacture name, device name,
dev. rev. #, and
DD rev. #>; HART application <version x.y> ...See
Programming Interface for details.
Hart Application Error..."data compression dll is
missing"...Reinstall System Files...See User's
Manual for details.
Description
An expected version of hc.ddl is not found.
The information describing the location of the
DDs is not found in the registry.
The HART Application finds voltage on the
fieldbus connector during initialization and
during reconnection to a device.
The HART Application fails to put the CDC in
HART mode for talking to a HART device.
The version of the tokenizer used to tokenize
the DD is not what the HART Application
expects.
The version of the linker used to link the DD
is not what the HART Application expects.
The DD was developed and tested using a
later HART Application revision.
The DD was not tested and verified with the
HART Application.
The DD was tested with a previous version,
but not with this version of the HART
Application.
The DD was developed using a later HART
Application revision.
There is a check sum error in the DD header
file.
The data compression component cannot be
located.