4-18
Display Network Settings
To view the network parameters for the device or
segment:
1. Display the Live Device List; see page 4-9.
2. Double-tap a device.
3. Double-tap Advanced.
4. Double-tap Network Management.
5. Double-tap the desired label to view the values.
Tap the SAVE button to save this as a text file. Transfer
this file to a PC using the Easy Upgrade Programming
Utility. The file appears in the User Data tab.
Change the I/O Block Schedule
NOTE
You cannot schedule I/O blocks when, at a minimum,
any of the following hosts/linking devices are detected
on the segment: Rosemount 3420, DeltaV, Ovation,
Allen-Bradley, Honeywell Experion PKS, or Yokogawa
Stardom. To schedule I/O blocks, use the host system or
remove the device from the segment and connect it
directly to the 375 Field Communicator.
To change the schedule:
1. Display the Live Device List; see page 4-9.
2. Double-tap a device.
3. Double-tap Advanced.
4. Double-tap Schedule. The I/O Block Schedule
window appears. Changing the I/O Block Schedule
would typically be done on the bench (not connected
to a control system) when you want to execute an I/O
block to verify that the outputs of the block are being
computed correctly.
5. Using the drop-down menu, select the appropriate
MacroCycle.
6. Tap the checkbox next to the I/O blocks that are to be
scheduled.
7. Tap OK. This will schedule the blocks and set the
mode on these blocks to Auto.
8. After reading the note, tap OK to acknowledge that
the I/O blocks were successfully scheduled.