Saving an
Online Device
Configuration
Displaying the
Device Setup
Submenu
When a configuration is saved from a connected device,
it is saved as a device configuration.
To save the configuration in the connected device:
1. Connect the 375 Field Communicator to a HART loop
or directly to the device and turn on the 375 Field
Communicator.
2. Double-tap HART Application from the 375 Main
Menu. The HART Online menu appears.
3. Tap Save.
a.To set the location where the configuration will be
saved, double-tap Location, select Internal Flash or
Configuration EM (Expansion Module), and tap
ENTER.
b.To enter a name for the configuration, double-tap
Name, type the name, and tap ENTER.
4. Tap Save. If the configuration already exists, a
message is displayed. Tap YES to overwrite the older
version with the new version, or tap NO to return to
the Save as screen.
The Device Setup menu accesses every configurable
parameter of the connected device. Double-tap Device
setup to view the process variables, diagnostics and
service, basic setup, detailed setup, and review menus.
Process Variables (PV)
The PV menu lists all process variables and their values.
Process variables are continuously updated when this
screen is displayed.
Diagnostics and Service
The Diagnostics and Service menu lists device and loop
tests as well as calibration options. The diagnostics and
service operations that are available vary widely from
device to device and are defined in the device
description.
The Test device menu lists the status as well as self and
master test of the device. Test device initiates a
diagnostic routine at the device and can report an
electronics failure, as well as other failures that can
affect performance.