Fieldbus Error and Help Messages
DDP Error 1: Unable to load DD. Press OK to return to
Block List
There has been a loss of communication with one or more
devices on the segment. Press OK to return to the live list.
The 375 has been disconnected from the segment. Press
RETRY to attempt to reconnect to the segment." Press
CANCEL to return to the FF app main menu. Press EXIT to
exit the FF App."
_T("SM ERROR: FAILED RESPONDER IDENTIFY")
_T("FFLIB: Incompatible DD Static Description")
_T("FBLIB: Device Upload aborted
_T("FMS OTHER: Parameter Check")
_T("FMS OTHER: Exceeds Parameter Limits")
_T("FMS OTHER: Wrong Mode For Request")
_T("SM ERROR: REMOTE ERROR INVALID STATE")
Troubleshooting
Description
Using Easy Upgrade, check to see if
this DD is available to load into your
375 unit. If not, contact the device
manufacturer.
Check connection to fieldbus
devices.
Verify that the 375 lead set is still
securely connected to the FF
Segment and press RETRY.
There is a problem sustaining
communications with the device.
Contact 375 Field Communicator
customer support personnel.
The Device Description (DD) does
not match the actual device correctly.
Use the 375 Easy Upgrade to see if a
new DD is available for that device.
Contact 375 Field Communicator
customer support personnel.
Communications with a device has
timed out. This should normally not
happen. Contact 375 Field
Communicator customer support
personnel.
The parameter being entered is
invalid for this device. Check with the
device supplier. Make sure the value
entered is valid for that specific
device parameter.
The parameter being entered is
outside the range of valid values for
the device parameter. Check with the
device supplier. Make sure the value
entered is in the correct range for that
device parameter
The block is in the wrong mode to
accept the parameter change being
requested. See "Modes" on page 4-4
on how to change block modes.
An attempt to change the address of
the device serving as the LAS on the
segment is being made. Changing
the device address of the LAS is not
recommended.