4-14
Displaying block parameters for
fieldbus devices
To display the parameters for fieldbus
devices:
1. Display the live list; see page 4-11.
2. Double tap a device on the live list to view
the blocks in that device.
3. Double tap the desired block.
4. Double tap the desired parameter group.
The parameters and their current values
are displayed. Shaded areas indicate
values that cannot be edited.

Changing and sending parameter data

To change the values for parameters:
1. Display the parameters for fieldbus
devices; see page 4-14.
2. Double tap the desired parameter.
3. Change the value for the parameter.
(Tap HELP to view a description of the
parameter.)
4. Tap OK to acknowledge the parameter
change. Repeat these steps for other
parameters as necessary. A "*" symbol
indicates a parameter has been edited.
5. Tap SEND to commit your changes to the
connected fieldbus device.
NOTE
The Block mode must be in the appropriate state to
accept parameter changes. Typically the mode is
MAN or OOS.