Step
Operation
DO AUTO
6
Set 0% value
DO AUTO
7
Set 100%
value
DO MAN
8
Set 0% value
9
DO MAN
10
Set 100%
value
11
Exit the
12
Calibration
Mode
5/00
Press
The decrement relay is turned on to move the motor to
FUNCTION
0% position.
LOOP 1/2
Upper Display: (Counts of Feedback Slidewire-0 to 3000)
Lower Display: ZERO VAL
When the motor stops, the display should stop counting,
then go to the next step.
The increment relay is turned on to move the motor to
FUNCTION
100% position.
LOOP 1/2
Upper Display: (Counts of Feedback Slidewire-0 to 3000)
Lower Display: SPAN VAL
When the motor stops, the display should stop counting,
then go to step 12.
You will see:
FUNCTION
LOOP 1/2
Upper Display: (The existing zero calibration value in
counts)
Lower Display: ZERO VAL
until the desired zero value is reached in the upper
or
display.
Upper Display: (The desired zero value)
Lower Display: ZERO VAL
The controller will store the 0% value and you will see:
FUNCTION
LOOP 1/2
Upper Display: (The existing span calibration value in
counts)
Lower Display: SPAN VAL
until the desired span value is reached in the upper
or
display.
Upper Display: (The desired span value)
Lower Display: SPAN VAL
For manual calibration, the motor does not move from its
position prior to the start of Position Proportional
calibration.
The controller will store the 100% value.
FUNCTION
LOOP 1/2
To exit the calibration mode.
LOWER
DISPLAY
or
SETUP
UDC3300 Expanded Model: DC330E User Manual
Position Proportional Calibration
Action
103