Installation
Position Proportional Output
Figure 2-13 shows models with Position Proportional Output (Model
DC330X-EE-XXX-X2) or Three Position Step Control (Model DC330X-AA-XXX-X2).
Calibration
Position Proportional Output models must have the output calibrated after
installation.
Three Position Step models only require that the motor time be entered. Full
calibration is not required.
Slidewire 100 to 1000
mechanically linked
to motor
2
Connect shield to ground
at one end only
1
Alarm #2 is not available with Position Proportional output or Three
Position Step control.
2
Do not run slidewire cable in the same conduit as AC power.
3
Electrical noise suppression may be required.
Slidewire input is not required for Three Position Step control but can be
4
used for motor position indication.
Figure 2-13 Position Proportional Output or Three Position Step—Models
14
4
3
Cl
Op
Wi
os
en
pe
ed
L1
Relay#1
L2/N
22
23
Relay#2
24
25
26
Relay#1
27
DC330X-EE-XXX-X2, DC330X-AA-XXX-X2
UDC3300 Expanded Model: DC330E User Manual
Motor Power
Supply
Neutral
Hot
5 Amp Fast Blo
fuse
Cl
Op
os
en
ed
1
N.C.
Output
2
N.O.
3
4
N.C.
Output
5
N.O.
1
6
7
N.C.
Alarm
Alarm Relay
8
#1 Load
N.O.
9
To terminal
7 or 9
Load
Supply
Power
5 Amp Fast Blo
fuse
5/00