Figure 2-3 Composite Wiring Diagram - Honeywell UDC3300 User Manual

Universal digital controller
Hide thumbs Also See for UDC3300:
Table of Contents

Advertisement

Installation
Composite Wiring
AC Line Voltage
Terminals
See Figure 2-4
Input #2 Terminals
See Figure 2-5
Two HLAI Terminals
See Figure 2-6
Input #1
Terminals
See Figure 2-5
Transmitter Power for
4-20 mA 2-wire
Transmitters
• Using Alarm 2 Output
See Figure 2-17
• Using Auxiliary Output
See Figure 2-18
Line Voltage Wiring
This equipment is suitable for connection to 90-264 Vac or 24 Vac/dc, 50/60 Hz,
power supply mains. It is the user's responsibility to provide a switch and non-time
delay (North America), quick-acting, high breaking capacity, Type F, (Europe) 1/2 A,
250 V fuse(s) or circuit-breaker for 90-264 V; or 1 A, 125 V fuse or circuit breaker for
24 Vac/dc operation, as part of the installation. The switch or circuit-breaker should
be located close to the controller, within easy reach of the operator. The switch or
circuit-breaker should be marked as the disconnecting device for the controller
2
(4 mm
).
CAUTION
Applying 90-264 Vac to a controller rated for 24 Vac/dc will severely damage the controller
and is a fire and smoke hazard.
6
10
L1
11
L2/N
12
22
13
23
14
24
15
25
16
26
17
27
I/O shield ground
(Do not use for
Communications shield)

Figure 2-3 Composite Wiring Diagram

UDC3300 Expanded Model: DC330E User Manual
Digital Inputs
Terminals
See Figure 2-15
1
2
• Current Output/Universal
3
4
5
6
7
For Control and Alarm Relay
8
9
Auxiliary Output
Communications
Terminals
See Figure 2-16
Outputs and Alarms
Terminals
• Time Proportional Output
See Figures 2-7, 2-8, 2-9,
2-10
Output
See Figures 2-11, 2-12
• Position Proportional
Output
See Figure 2-13
Contact information, See
Tables 2-3 and 2-4.
Terminals
See Figure 2-14
5/00