Position Proportional Calibration
Step
Operation
Enter
1
Calibration
Mode
Set Motor
2
Traverse
Time
3
Select
4
Automatic or
Manual
Calibration
5
102

Table 9-1 Calibration Procedure

Press
until you see
SETUP
Upper Display: CALIB
Lower Display: POS PROP
Until you see
FUNCTION
LOOP 1/2
Upper Display: (A value)
Lower Display: MTR TIME
NOTE: This is the time it takes the motor to travel from 0
to 100%.
until the proper motor stroke time is reached (see the
or
motor specs or measure the time)
Range of setting = 5 to 1800 Seconds
Until you see
FUNCTION
LOOP 1/2
You can calibrate the controller output manually or let the
controller calibrate the output automatically.
If the slidewire has never been calibrated, you must use
DO AUTO first. In the "Automatic Calibration Mode" (DO
AUTO), the controller relays automatically move the motor
in the proper direction.
If desired, however, the motor may be manually
positioned to 0% and 100% positions. Disconnect the
relay wires. Use DO MAN. In the "Manual Calibration
Mode" (DO MAN), the motor does not move. Instead, the
existing 0% and 100% values may be changed with the
or
to select automatic or manual calibration.
or
Upper Display: DO AUTO or DO MAN
Lower Display: POS PROP
If you select...
DO AUTO
DO MAN
ATTENTION
selection reverts to DISABL.
UDC3300 Expanded Model: DC330E User Manual
Action
key.
Then...
go to Step 6
go to Step 8
When calibration is terminated, this