5.3 Setpoint Ramp/Soak Programming Option

Introduction
Setpoint Ramp/Soak Programming lets you configure six ramp and six soak
segments to be stored for use as one program or several small programs. You
designate the beginning and end segments to determine where the program is to
start and stop.
Review Program Data and Configuration
The procedure for programming is straightforward and aided by prompts. We
suggest that you read Table 5-2 which lists the program contents with an
explanation of each to aid in configuration. Then refer to Section 3.5 – SP Ramp, SP
Rate, or SP Programming Set Up Group to enable and configure the setpoint
program.
ATTENTION
SP RATE and SP RAMP must be disabled to enable SP PROG (Setpoint Programming).
Fill Out the Worksheet
Referring to the example in Figure 5-1, draw a Ramp/Soak Profile on the worksheet
provided in Figure 5-2 and fill in the information for each segment. This will give you
a record of how the program was developed.
Operation
See Table 5-3 to run/monitor the program.
Power Outage
ATTENTION
If power is lost during a program, upon power-up the controller will be in hold and the
setpoint value will be the setpoint value prior to the beginning of the setpoint program. The
program is placed in hold at the beginning of the first segment in the program. The mode
will be as configured under PWR MODE in the Control function group. (This applies to both
loops.)