1.4.3

Municipal Circuit Option Module (MCOM)

The MCOM Module can trip a Local Energy City Master Box, or operate in
reverse polarity mode for leased line connection. It can also energize a solenoid
for releasing.
1.4.4

Printer Transient Module (PTRM)

The serial output on the BSM is connected via an existing RS-232 RJ-11
connector, J3. This can be used to communicate to the control with a laptop
computer while at the panel. The PTRM module is intended for systems where a
permanent connection is required. This type of connection requires that the RS-
232 port have sufficient transient protection to comply with the applicable codes
for wiring leaving the confines of the control box, as well as the proper isolation of
the signal to prevent damage or interference caused by the connection to certain
EDP devices. Connections are limited to the same room. The PTRM supplies
supervision and transient protection as well as the necessary isolation.
1.4.5

LCD-7100 Remote Serial Annunciator Module

The LCD-7100 Serial Remote Annunciator provides an 80-character display and
function keys for "Alarm Acknowledge", "Trouble Acknowledge", "Signal Silence",
"System Reset/Lamp Test" and "System Drill Test".
The 80-character display shows all pertinent information except for menus.
1.4.6

LDM-7100 Remote LED Driver Module

Each LDM-7100 LED Driver Module provides 7100 Control Panel output for
thirty-three (33) remote LEDs. Three (3), LDM-7100 modules may be mounted in
a single annunciator for a maximum total of 99 points per annunciator.
The annunciator may be located up to 4,000 feet from the panel and up to four
(4), additional annunciators can be connected, configured identically with the
first.
1.4.7

INI-7100-UTP, Intelligent Network Interface, Unshielded, Twisted-Pair

E3 Broadband Network interface to the 7100 FACP using copper wire network
terminations only. It occupies one node on the E3 Series
1.4.8

INI-7100-FO, Intelligent Network Interface, Fiber-Optic

E3 Broadband Network interface connection to the 7100 FACP using either fiber-
optic cable or copper wire network terminations. It occupies one node on the E3
Broadband Network.
Note: The Network Graphic Annunciator Module (NGA) is required when more
than seven (7), 7100 Series panels are networked. See the E3 Broadband
Installation/Operating Manual Part Number: 9000-0575 for details.
1.5

Specifications

Power Supply Output
Supervisory current
Alarm current
9000-0447 Rev. I
OR
1.0 amp. (max.) (24 VDC nominal)
3.335 amp. (max.) (24 VDC nominal)