Honeywell Gamewell 7100 Series Installation & Operating Manual page 36

Fire alarm control
Table of Contents

Advertisement

Main
Config
Global
Codes
Main
Config
Global
System ID
or
Main
Config
Inputs (or Outputs)
Select
Location
Main
Config
Global
Misc. [6]
Main
Config
Global
Misc. [7]
NOTE:
Some menus may appear in different contexts, but with slightly different behavior. For example,
the "Select Device" menu is used in both the Config Inputs and Config Outputs sections to
determine which device is to be affected. The process of selection is the same, but when the
selection is complete, the result (that is, which menu opens next) differs.
NOTE: The Alarm Verification Feature is disabled when sensor cross-zoning is employed.
9000-0447 Rev. I
[CODED] 1: Set Day Alarm (MT60)
[PATTS]
to select condition
<>: selects response condition from: Day Alarm, Night Alarm,
Action, Supervisory, Aux.
1: Scrolls through coded pattern selections: MT60, MT120,
Temporal, CA Code, Coded 4s.
[L,AAA]
[LOCTN] 7,9 chng 1st ^
Enter label using keypad and shift key. Press button until
desired letter appears. Use BKSP/EDIT to capitalize.
Use arrow keys <> to shift message from left to right or vice
versa.
NOTE: If this menu is opened from the Global Config Menu,
System ID selection (Menu 5 option 4), SYSTM ID is displayed;
otherwise, L,AAA LOCTN as shown above.
1: Toggles Multiple Trouble Acknowledge ON/OFF
2: Toggles Alarm/Trouble Reminder ON/OFF
3: Scrolls Walk Test Timeout (30m, 60m, 90m)
4: Toggles RS232 Supervision Message ON/OFF
[MISC] 1: MutiAck (ON)
[OPTS] 3: WT Timeout (30m)
[LCD] Number of Remote Displays (1)
[Annunc]
Page 30 of 42
Config
FLR1 Lobby
chng 2nd
2: Reminder (ON) Config
4: SupvMsg (ON)
Config