3.12 7100-D DACT Event Reporting Codes

The 7100-D DACT event reporting codes are shown in Table 3-6 below:
Event
Fire Alarm (Smoke or Manual Station)
Fire Alarm Restored
Waterflow Alarm
Waterflow Alarm Restored
Trouble (except Waterflow or Special AMM)
Trouble Restored
Trouble (Waterflow AMM)
Trouble Restored (Waterflow AMM)
Trouble (Special AMM)
Trouble Restored (Special AMM)
Supervisory / Tamper (Module)
Supervisory Restored (Module)
PAS/Action/Supervisory (Sensor)
PAS/Action/Supervisory Restored (Sensor)
Disable (except Waterflow or Special AMM)
Disable Restored
Disable (Waterflow AMM)
Disable Restored (Waterflow AMM)
Disable (Special AMM)
Disable Restored (Special AMM)
AC Fail
AC Fail Restored
Phone Line 1 Fault
Phone Line 1 Fault Restored
Phone Line 2 Fault
Phone Line 2 Fault Restored
Automatic Test (NORMAL)
Automatic Test (With Exception)
For Contact ID and SIA Formats:
GG = group number assigned to the device, 00-99
(For networked systems, GG = Node number)
T
= Type of device or event causing the event to be reported.
0= Non-loop event
1= Any event or device type not listed below
2= Manual Station
3= Supervisory Device (Non-latching)
4= Supervisory Device (Latching)
5= Waterflow (Non-silenceable)
6= Smoke Alarm
8= Multilevel Device
Note:Special AMMs include the following functions:
Reset Switch, Silence Switch, Drill Switch, Alarm Acknowledge Switch, Trouble Acknowledge
Switch.
9000-0447 Rev. I

Table 3-6 DACT-E3 Event Reporting Codes

Page 20 of 42
SIA
Contact ID
FA GGT
1 110 00 GGT
FH GGT
3 110 00 GGT
SA GGT
1 113 00 GGT
SH GGT
3 113 00 GGT
FT GG0
1 373 00 GG0
FJ GG0
3 373 00 GG0
ST GG0
1 370 00 GG0
SJ GG0
3 203 00 GG0
UT GG0
1 370 00 GG0
UJ GG0
3 370 00 GG0
SS GGT
1 203 00 GGT
SR GGT
3 203 00 GGT
FS GGT
1 200 00 GGT
FR GGT
3 110 00 GGT
FB GG0
1 571 00 GG0
FU GG0
3 571 00 GG0
SB GG0
1 570 00 GG0
SU GG0
3 570 00 GG0
UB GG0
1 570 00 GG0
UU GG0
3 570 00 GG0
AT 0
1 301 00 000
AR 0
3 301 00 000
LT 1
1 351 00 000
LR 1
3 351 00 0000
LT 2
1 352 00 000
LR 2
3 352 00 000
RP 0
1 602 00 000
RP991
1 602 00 991
4/2
3/1
0T
0
2T
2
0T
0
2T
2
8T
8
7T
7
8T
8
7T
7
8T
8
7T
7
6T
6
7T
7
6T
6
7T
7
8T
8
7T
7
8T
8
7T
7
8T
8
7T
7
8T
8
7T
7
81
8
71
7
82
8
72
7
90
9
91
9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gamewell-fci 7100 series

Table of Contents