Table 5-1 7100 Series Menu System - Honeywell Gamewell 7100 Series Installation & Operating Manual

Fire alarm control
Table of Contents

Advertisement

Menu Tree
Main
Main
Config
Main
Config
Auto
Main
Config
Global
NOTES:
1) In general, "BACK" exits the current menu and returns it to the previous menu without
changing any settings. "OK" accepts any changes that have been made and returns to the
previous menu, except in special cases where it continues to the next menu in a group. (See
Menu 35).
2) The Set/View Configuration functions use the same menus, but behave differently depending
on the Main menu selection and password given. If the "Config" option is selected and a valid
Level 4 password is entered, the menus are fully operational. If the "Views" option is selected,
or if the password is not valid for Level 4, then the menus may be examined but no changes
can be made.
9000-0447 Rev. I

Table 5-1 7100 Series Menu System

[MAIN] 1: Config 2: Walk/Drill 3:I/O
4: Clock 5: View 6: Log 7:Info
1: Opens System Config Menu (PW-L4 required)
2: Opens Walk Test / Drill Menu (PW-L1 required)
3: Opens I/O Control Menu (PW-L2 required)
4: Opens Set Clock Menu (PW-L1 required)
5: Opens System Config Menu for viewing only
(PW-L3 required)
6: Opens Event Log Menu (PW-L1 required)
Note: View option is identical to the Config option,
allowing access to all the configuration menus, but
prevents changing of any settings. The limiting factor
between View and Config is the password level used.
[SYSTEM] 1: Auto 2: Global 3: Inputs
[CONFIG] 4: Outputs 5: Groups 6: Passwords
1: Opens Autoconfig Menu
2: Opens Global Config Settings Menu
3: Opens Select Input Device Menu
4: Opens Select Output Device Menu
5: Opens Select Group Menu
6: Opens Change Password Menu
[AUTO-
] 1: Clear, then ... 2: Update SLCs
[CONFIG]
1: Clears system configuration, then reads SLCs.
2: Reads SLC, finds changes. New devices get default
config, missing devices are marked off-line. No change to
globals or groups. (via confirm screen)
[GLOBAL] 1: I/O Devices 2: NACs 3: Codes
[CONFIG] 4: System ID
1: Opens Device Defaults Menu
2: Opens NAC Settings Menu
3: Opens Coded Pattern Setup Menu
4: Opens System ID Menu
5: Opens Dialer Settings Menu
6, 7: Opens Misc. Globals Menus
Page 28 of 42
Display and Selections
5: Dialer
6: Misc.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gamewell-fci 7100 series

Table of Contents