Honeywell Gamewell 7100 Series Installation & Operating Manual page 14

Fire alarm control
Table of Contents

Advertisement

Battery Connection (TB7)
• Supervised
• 24 VDC nominal
• Maximum battery size 31 AH
• Non-power-limited
• 0.6 A max. battery charge current
The RS-232 port, consists of an RJ11 connector which provides a standard serial port for
the connection to a Listed output device for supplementary type service. Typical
examples of such devices include any UL Listed EDP device (remote printer or video
terminal), any UL Listed Signaling Device (such as the Keltron VS4095/5 printer), or any
UL Listed Signal System Unit.
Ratings:
Connections to the RJ11 serial connector are as follows:
Terminal
2
3, 4
5
6
Available cables for RS-232 connection are:
Part No.
6100-0077
6100-0074
6100-0075
6100-0076
NOTE: The BSM is shipped with jumpers installed on the middle three pairs of pins on
J2. These jumpers must be removed when the PTRM is installed.
9000-0447 Rev. I
15 VDC (max.)
.05 amp. (max.) current
9600 baud
8 bits, 1 stop bit, no parity.
Description
RXD
GND
TXD
Supervision
Model
RJ11-DB9PC
RJ11-DB25
RJ11C-6
RJ11C-20
Figure 4
Page 8 of 42
Description
RJ11 to 9-pin DB9
(Connector only - PC Laptop)
RJ11 to 25-pin (DB25) (connector only-printer)
RJ11 to RJ11 cable, 6-inches
RJ11 to RJ11 cable, 20 feet
1
2
3
4
5
6
Figure 3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gamewell-fci 7100 series

Table of Contents