5.2

CONFIG. Menu Selections

AUTO
GLOBAL
INPUTS
OUTPUTS
GROUPS
DIALER
NOTE:
The DACT account programming options for Alarm, Test, Trouble and Supervisory
events are defaulted to "MUST" in the Reporting Options section. In order to use this
panel for remote signaling purposes all events must be transmitted off-premises.
If one account is used, it is required that the Reporting Option for each event (Alarm,
Test, Trouble, Supervisory) be set to "MUST". If two accounts are used, it is required that
the reporting option for each event be set to "MUST" between the two accounts.
Reporting options for each event (Alarm, Test, Trouble, Supervisory) are as follows:
OFF
Event will not be reported to the account.
CAN
Event can be reported to this account.
MUST
Event must be reported. The DACT will continue to attempt to report
this condition until all attempts have been made. If the DACT cannot
report the event, the event will remain in the system memory and will be
retransmitted with a subsequent event.
9000-0447 Rev. I
Is the selection used to either initialize
the system or update it.
Is the key feature to the simplicity of
programming. Most system as well as
individual SLC device programming
can be accomplished here.
Allow the user to insert point-to-point
address information to sensors and
monitor points individually for device
type, location, input group(s), and to
modify any of the global programming.
Gives
the
same
capabilities supplied to the inputs.
Supply the option to allow either Alarm
or Supervisory devices access to the
system general output list for each
type
(General
Alarm
Supervisory outputs).
Configuration gives the user the ability
to turn the DACT on, program primary
and secondary phone numbers and
accounts, the format that the receiver
requires, as well as the event types
that are or are not transmitted.