3.18 Optional Accessories

3.18.1 LCD-7100 Serial Remote Annunciator

The LCD-7100 Serial Remote Annunciator provides an 80-character display and
function keys for the following:
- "Alarm Acknowledge"
- "Trouble Acknowledge"
- "Signal Silence"
• The 80-character display shows all pertinent information except for menus.
• Keypad functions are enabled only when the keylock is turned to the
"Unlocked" position, with the exception of the "Trouble Acknowledge" switch
which silences the local audible trouble sounder.
• Operating LEDs provided are as follows:
- "Alarm"
- "Supervisory"
- "System Trouble"
• The LCD-7100 is flush or surface-mounted on a standard 4-gang electrical box.
• The 7100 Series control can accommodate up to five (5), remote LCD-7100
annunciators which may be located up to 4,000 feet from the main control
panel. See Table 3-7 below for resistance limitations of the connecting circuit.
No. of LCD-7100 Units
Max resistance of 24 VDC power
circuit (ohms) to most distant LCD

3.18.2 LDM-7100 LED Driver Module

Each LDM-7100 LED Driver Module provides 7100 Control Panel output for
thirty-three (33), remote LEDs. Three (3), LDM-7100 modules may be mounted in
a single annunciator for a maximum total of 99 points per annunciator.
The annunciator may be located up to 4,000 feet from the panel and up to four
(4), additional annunciators can be connected, configured identically with the
first. See Table 3-8 for resistance limitations for the connecting circuit.
Note, that if more than four (4), LDM-7100 modules are installed, an external
regulated and power-limited power supply Listed for use with fire protective
signaling units is required.
The module is intended for mounting inside the enclosure of a UL Listed remote
annunciator. It may be mounted by means of mounting screws or stacked using a
metal hex standoff kit. Wire routing and installation methods are to be in
accordance with the annunciator installation instructions.
Qty. of LDM-7100 modules
Max resistance of 24 VDC power
Circuit (ohms) to most distant LDM
NOTE 1: Maximum attenuation for the entire fiber-optic line is 8 dB.
NOTE 2: The use of fiber-optic cable is not permitted in New York City.
9000-0447 Rev. I
- "System Reset/Lamp Test"
- "System Drill Test"
- "Power Fault"
- "System Silenced"

Table 3-7 Resistance Limitations

1
2
70
38
Table 3-8 Resistance Limitations
1
40
Page 22 of 42
- "NAC #1 Silenced"
- "NAC #2 Silenced"
3
4
5
24
17
4
2
3
4
5
to
20
14
10
See above.