6.0

Power Up Procedure

6.1

General

Ensure that all cables and optional modules (if any) are installed and secured per the
installation instructions. DO NOT install any field wiring at this time.
1. Connect the End-of-Line devices to the notification appliance and municipal (if
installed) circuits.
2. Power the panel with AC first. The system initializes and indicates a "Battery Missing"
condition.
3. Connect the batteries, taking care to observe polarity.
4. The system should be in normal condition. You may proceed with the installation of
field wiring. Check all wiring prior to the connection to the control panel. Do not use
this panel as a circuit tester.
6.2

To set the system time (Keyswitch must be engaged).

1. Press the MENU/Back button on the keypad and enter the Level 1 password,
XXXXXX.
2. Press the OK button.
3. The Main Menu displayeds. Press the Number 4 and the Clock Menu displays.
4. The following table includes the numbers and the purpose of each number.
Number 1
Number 2
Number 3
Number 4
Number 5
Note: Use the keypad to enter the data. Use the OK button when each section is
completed. The OK button acts as an Enter Key.
5. Press the Reset/Lamptest button and ensure that the time and date remain correct.
6.3

Automatic Configuration

1. Press the Menu/Back button on the keypad and enter the Level 4 password,
YYYYYY.
2. Press the OK button.
3. The Main Menu displays. Press the Number 1 and the Configuration Menu displays.
4. Press the Number 1 to open the Automatic Configuration Menu. Numbers 2 through
5 are for specific programming and are covered in previous sections.
5. Since this is the first time the system is being configured, press the Number 1 to
initiate the Clear, Then Configure process. This will place all of the system settings
to the factory default and then read all of the devices correctly connected to the two
(2), SLCs. After this process is complete, the system may be given an initial test to
assure all of the devices have been installed into the system memory.
NOTE: Automatic configuration does not set the DACT. The DACT must be programmed.
9000-0447 Rev. I
Opens the Time setup.
Opens the Date setup.
Opens the Day/Night setup.
Opens the Weekend setup.
Opens the Holiday setup.
Page 40 of 42