Honeywell Gamewell 7100 Series Installation & Operating Manual page 37

Fire alarm control
Table of Contents

Advertisement

Main
Config
Inputs or Outputs
_______________or_________
Main
I/O
Control or Ena/Dis
Main
Config
Inputs
Select
Main
Config
Inputs
Select
Type
Inputs
Select
Group
Input
Select
Verify
Inputs
Select
Sens
Inputs
Select
View
9000-0447 Rev. I
[SELECT] Loop, Address: 1,001
[DEVICE] Key in or use <,>
# keys: enters SLC & address (restriction: Address 200)
<>: Scrolls up or down to next available device.
OK: Accepts address, opens Configure Input Device Menu,
Configure
Output
Device
Enable/Disable Device Menu, as appropriate.
[CONFIG] 1: Type 2: Group 3: Verify 4: Sens
[L, AAA] 5: Location 6: View 7: Copy L, AAA
1: Opens Set Input Type Menu.
2: Opens Assign Input To Group Menu.
3: Opens Set Verify/PAS Function Menu (sensors only).
4: Opens Set Sensitivity Menu (Ion, Photo devices only).
5: Opens Set SLC Device Location Menu.
6: Displays all settings for current device.
7: Copies all settings of the specified device (last input modified)
[L, AAA] Ion Duct Det
[TYPE
]
^
Key in Input Type # or use <,>
<>: scroll through types which match this physical device.
# keys: enter type number (no restrictions; see Type Table)
Shows type and associated Response.
BKSP/EDIT: If selected device type is editable, or if it is not editable
but there is room to create a new user-editable type, opens Add
Type menu (Menu 35). ^indicates that editing is possible.
[L,AAA]
Group 007
[GROUP]
Key in Group#
No restrictions on group assignment.
[L,AAA] 1: Verification
Options are: Default, None, Smoke Verify (Ion/Photo only), PAS
[L,AAA] 1: Day Sensitivity
[SENS ] 2: Night Sensitivity
1: Scrolls through Day Sensitivity options.
2: Scrolls through Night Sensitivity options.
Options vary by type, may include: Default, 1.00%, ...2.00%
[L,AAA] Ion Duct Det
Alarm Grp23 Vfy:Default 1.75%
Shows: SLC and Address, Device Type, Location Label, Device
Response, and I/O Group. Shows Verify/PAS settings and day
sensitivity setting if applicable (if device is set for default sensitivity,
shows default day sensitivity). No changes can be made.
Page 31 of 42
Menu,
Control
Output
01
(Alarm)
(00=no group)
or use <,>
(Default)
(Default)
(Default)
FLR2
Storeroom
Menu,
or