Appendix B Ratings And Specifications - GE EX2100 User Manual

Excitation control
Table of Contents

Advertisement

Appendix B Ratings and
Specifications
EX2100 Specification
Power Conversion Module (PCM)
Single bridge rating
Parallel bridge rating
Forcing requirements
Power Sources
Power for the PCM – Voltage source
Power for the PCM – VA (power)
Power for the PCM - Frequency
Power to the Cooling Fans (3)
Flashing power
Control power (redundant with 2 bridges,
warm backup}
Heat loss in single PCM cabinet
EX2100 User's Guide GEH-6632
The actual equipment rating is on your exciter nameplate.
This appendix indicates the range of possible product
offerings but not necessarily the capability of your exciter.
Description
1,000 and 2,000 A dc at up to 1,000 V ac
8,000 A dc at up to 1,500 V ac, with up to 6 bridges
150% of design Amperes (EDA) for 30 s at 40 ºC
Auxiliary bus
Generator terminals
Compound Source
600 or 1,000 V versions
3,251 KVA (1,000 V version)
3-phase 50/60 Hz, ± 5%
10 A rms, 125 V ac single source
125-250 V dc battery source, with up to 200 A for at least 10 s
380-480 V ac, 50/60 Hz single-phase auxiliary source
For two ac sources, or one ac and one dc source
Nominal 120 V ac ±15%, with 1 DACA, 10 A rms max.
Battery source 125 V dc, range 80-140 V dc, 10.6 A dc max.
10 KW for a 2000 A, 1,000 V ac PCM
Appendix B Ratings and Specifications B-1