GE EX2100 User Manual page 82

Excitation control
Table of Contents

Advertisement

Group
Icon
Heartbeat
Control
Blank
Fault State
blinking
o
Status
5-6 Chapter 5 Diagnostic Interface-Keypad
Table 5-3. Exciter Health and State Icons
Indication
Description
Communications
Animated line (its center raises and lowers) shows that there is
OK
communication between the keypad and the exciter.
Communications
Animated metronome icon shows that the keypad is attempting to
not established
establish communication with the exciter, but cannot.
Auto mode
Regulates terminal voltage.
Manual mode
Regulates field voltage.
Test Mode
The exciter is performing a diagnostic test.
Exciter OK
When no icon displays, the exciter is operating correctly.
Abnormal
Displayed when there are over-ridden parameters.
Alarm state
Displayed when an alarm condition occurs.
Trip fault
Displayed when a fault state occurs.
Stopped
Exciter is stopped.
Running
Exciter is running.
Field voltage regulator output is greater than field current regulator
Limiting
or V/Hz or UEL limits are active.
Offline
Exciter is offline.
Online
Exciter is online.
GEH-6632 EX2100 User's Guide