Input/Output
Potential transformers (PTs)
Current transformers (CTs, 1 or 5 A)
86G dedicated contact input
52G dedicated contact input
Trip rated contact outputs
General Purpose contact inputs
General Purpose Form C contact outputs
± 10 V differential amplifier input
Thermal
Base controls cabinet
Base power conversion and auxiliary
cabinet
Cabinet Dimensions & Weight
Redundant control with dual PCM
redundant converter in a three-cabinet
lineup
Weight of Converter cabinet
Weight of Total Lineup (Converter,
Control, and Auxiliary cabinets)
Cabinet type, control & auxiliary
enclosures
Cabinet type, power conversion
Power and Control Cable Access
EX2100 User's Guide GEH-6632
QTY
2
3-phase standard, single phase available
120 V ac nominal
1 VA nominal burden
2
Any two phases, single phase available
1 VA nominal burden
1
open for trip
1
closed for online
2
At 125 V dc with relay break characteristics:
Resistive load 0.5 A
Inductive load 0.2 A
6
Customer contacts, 70 V dc supplied by ECTB
4
At 125 V dc with relay break characteristics:
Resistive load 0.5 A
Inductive load 0.1 A
1
Continuous operation in a 0 to 40 ºC ambient environment, with 5 to
95% humidity, non-condensing
Continuous operation in a 0 to 40 ºC ambient environment, with 5 to
95% humidity, non-condensing
Width 141.74 in (3600 mm)
Height 104.32 in (2650 mm)
Depth
31.5 in (800 mm)
3,600 lbs
5,600 lbs
NEMA 1 (IEC IP 20), convection cooled
NEMA 1 (IEC IP 20), forced air cooled
Entrances from the top and/or bottom