DCA-125USJ (50 HZ)— GENERATOR SHUT-DOWN PROCEDURE
CAUTION
CAUTION
CAUTION
CAUTION:
CAUTION
NEVER stop the engine suddenly except
in an emergency. DO NOT use the
emergency stop switch a as method of
shutting down the generator. This switch is
ONLY to be used in the event of an
emergency.
Shutdown Procedure
To shutdown the generator use the following procedure:
1. Place both the MAIN, GFCI and LOAD circuit breakers
as shown in Figure 39 to the OFF position.
3. Let the engine cool by running it for 3-5 minutes with no
load applied.
4. Place the MPEC Control Switch (Figure 55) to the
OFF/RESET position.
Figure 55. MPEC Control Switch (Off/Reset)
5. Verify that the all status LED on the MPEC display
are OFF (not lit).
6. Remove all loads from the generator.
PAGE 42 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV. #0 (03/11/05)
Emergency Shutdown Procedure
1. To shut-down the engine in the event of an emergency,
switch the MAIN , GFCI and LOAD (Figure 39) circuit
breakers to OFF position.
2. Place the MPEC Control Switch switch (Figure 55) to
the OFF/RESET position.