DCA-125USJ (50 HZ)— OUTPUT TERMINAL PANEL FAMILIARIZATION
Connecting Loads
Loads can be connected to the generator by the Ouput Terminal
Lugs or the convienience receptacles. (See Figure 13). Make
sure to read the operation manual before attempting to connect
a load to the generator.
To protect the output terminals from overload, a
3-pole, 300A main circuit breaker is provided. Make sure to
switch ALL circuit breakers to the OFF position prior to
starting the engine.
Figure 13. Connecting Loads
Over Current Relay
An over current relay (Figure 14) is connected to the main
circuit breaker. In the event of an overload, both the circuit
breaker and the over current relay may trip. If the circuit
breaker can not be reset, the reset button on the over cur-
rent relay must be pressed. The over current relay is lo-
cated in the control box.
Figure 14. Over Current Relay
PAGE 28 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV. #0 (03/11/05)
Blower Fan
This unit has an intake fan located at the rear of the machine
to draw outside air into the cabinet to cool the engine. The
fan has a 10 amp AC fuse located beneath the Voltage
Selector Switch (Figure 15).
Figure 15. Blower Fan Fuse
DANGER:
This fuse has current running through it any
time the engine is operating. THIS FUSE
IS NOT connected to the main circuit
breaker OF the generator. Attempting to
replace the fuse with the engine
and/or generator operating could
result in electrocution and severe
bodily harm . ALWAYS turn the
unit completely off before
attempting to replace or handle
THIS fuse