Generator Start-Up Procedure (Manual) - MULTIQUIP ULTRA-SILENT DCA-125USJ Operation And Parts Manual

Ultra-silent series 50 hz generator
Hide thumbs Also See for ULTRA-SILENT DCA-125USJ:
Table of Contents

Advertisement

DCA-125USJ (50 HZ)— GENERATOR START-UP PROCEDURE (MANUAL)
WARNING:
WARNING:
WARNING:
WARNING:
WARNING:
The engine's exhaust contains harmful
emissions. ALWAYS have adequate
ventilation when operating . Direct exhaust
away from nearby personnel.
Before Starting
CAUTION:
NEVER! manually start the engine with the
main , GFCI or auxiliary circuit breakers in
the ON (closed) position.
1. Place the main, G.F.C.I. and aux. circuit breakers (Figure 39)
in the OFF position prior to starting the engine.
Figure 39. Main, Aux. and GFCI
Circuit Breakers (OFF)
2. Connect the load to the receptacles or the Output
Terminal Lugs as shown in Figure 13. These load
connection points can be found on the output terminal
panel and the output terminal panel's hard wire hookup
panel.
3. The output terminal lugs are protected by a plastic cover.
Remove this cover to gain access to the terminals.
Tighten terminal nuts securely to prevent load wires from
slipping out.
PAGE 38 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV. #0 (03/11/05)
4. Close all engine enclosure doors (Figure 40).
Figure 40. Engine Enclosure Doors
5. Place the voltage selector switch
in the desired voltage position
(Figure 41).
Figure 41. Voltage Selector
Switch

Advertisement

Table of Contents
loading

Table of Contents