DCA-125USJ (50 HZ)— GENERATOR START-UP PROCEDURE (AUTO MODE)
DANGER:
Before connecting this
generator to any
building's electrical
system, a licensed
electrician must install an isolation (transfer) switch .
Serious damage to the building's electrical system may occur
without this transfer switch.
CAUTION:
When connecting the generator to a
isolation (transfer) switch, ALWAYS have
power applied to the generator's internal
battery charger. This will ensure that the
engine will not fail due to a dead battery.
NOTE
WARNING:
When running the generator in the AUTO
mode, remember the generator can start
up at any time without warning. NEVER
attempt to perform any maintenance when
the generator is in the auto mode.
1. Perform steps 1 through 5 in the Before Starting section
as outlined in the Manual Starting Procedure .
DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV. #0 (03/11/05) — PAGE 41
When the generator is set in the
AUTO mode, the generator will
automically start in the event
of comercial power falling below
a prescribed level by means of
a contact closure that is
generated automatically by a
transfer switch.
Starting (Auto Mode)
2. Place the MPEC Control Switch (Figure 54) in the
AUTO position .
Figure 54. MPEC Control Switch (AUTO)
3. Continue to follow the steps outlined in the Manual Start-
up procedure (start at step 9).