START EXIT TIME
If the central station ringback signal has not been received within about 30 seconds, a communication problem may exist.
Press YES (
button) to start exit delay manually.
E
FAULT FIND
This troubleshooting aid will help the installer locate swingers. When accessed, two things occur:
!
The loop response of each zone is set for the fastest response time.
!
Causing or repairing a fault activates the sounder for about 7 seconds.
Tapping and poking at suspect points, the installer can easily locate swingers by listening for the beep. This eliminates
the need of returning to the keypad to visually check after each attempt. Pressing the
operation. Arming the system automatically cancels the Fault find Mode. Note: When testing wireless systems, the
keypad will not beep if the signal strength is less than 3, but the strength will still be displayed.
ACTIVATE LOCATE
This feature will help the user find zone troubles and indicate when they are repaired. When accessed, the sounder will
come on and the display will read "LOCATE", then scroll through the zones in trouble. As each zone is corrected, the
sounder will stop momentarily, signaling its repair, and the display will indicate the remaining zones in trouble. The
sounder and display will continue in this manner until all zones are repaired, or until the
EZM ZONE FIND
To find the physical location of an EZM, enter the number of any zone on that EZM, then press the
cause the EZM sounder to pulse continuously until silenced. To silence the sounder, press the
keypad.
ACTIVATE DIALER TEST
Press YES to send a digital dialer test code to the central station using the system account number. (Be sure to notify the
central station of the impending test.) A successful test will clear a Failure to Communicate system trouble.
The History Log documents the 800 most recent events.
DISPLAY ALARM LOG
Displays most recent alarm events. Line 1 displays event and date. Line 2 displays time, area and zone. To check
previous alarm events, scroll back using the PRIOR (
DISPLAY TOTAL LOG
Displays most recent events of all types. Line 1 displays event and date. Line 2 displays time and, if applicable, area and
zone or user. To check previous events, scroll back using the PRIOR (
DISPLAY FIRE LOG
Displays most recent fire events. Line 1 displays event and date. Line 2 displays time, area and zone. To check previous
fire events, scroll back using the PRIOR (
DISPLAY OP/CL LOG
Displays most recent openings and closings. Line 1 displays event and date. Line 2 displays time, area and user. To
check previous events, scroll back using the PRIOR (
DISPLAY SYSTEM LOG
Displays most recent system events. Line 1 displays event and date. Line 2 displays time and other pertinent information,
where necessary, depending upon event. To check previous system events, scroll back using the PRIOR (
button.
L
NAPCO Security Systems
) button.
F
) button.
F
) button.
F
button to restore normal
C
button is pressed.
C
) button.
F
X
GEM-X255 Installation Instructions
!
Page 27