Extinguishing Panel - INSTRUCTION MANUAL

Controls

The Premier EX8 has the following controls:-
LABEL
USE
START/STOP
Used to silence the sounders in an alarm, or to manually start the FIRST
STAGE sounders to evacuate building
SILENCE FAULT
Used to silence the panel`s internal buzzer in a fault or alarm condition.
TONE
RESET
Used to return the panel to its normal condition after an ALARM condition.
(Reset will not clear faults)
LED TEST
To check that all indicator LEDs are working. Use as part of the daily / weekly
fire alarm inspection.
DISABLE
Used to access Disablement mode
DISABLE –
Used to scroll to select which part of the system to disable
SELECT
DISABLE –
Used to confirm disablement of the highlighted part of the system.
CONFIRM
TEST
Used to access test mode
TEST – SELECT
Used to scroll to select which part of the system to test
TEST – CONFIRM
Used to confirm test mode of the highlighted part of the system.
AUTO / MANUAL
Used to toggle between automatic & manual only mode
GAS RELEASE
Used to view or alter Gas Release Counter
COUNTER
RELEASE
Used to view or alter Release Duration Time Counter
DURATION TIME
RESET INHIBIT
Used to view or alter Reset Inhibit Time Counter
TIME
0-9
To enter access code & timer values
ENTER
To confirm new timer setting
CANCEL
To Save an edited time and exit from the timer set-up.
Note that the controls can only be used after the keyswitch has been turned to the
ON position.
***When the manual release call point on the front of the panel is operated, all
panel controls will be inoperative. It`s element will need to be reset before the
panel can be reset***
Approved Document No: GLT.MAN-124
Issue : 1
Author: NRPJ
Date: 15/11/2007
PAGE 7