Mains & Battery

Connecting the mains.

The Mains supply to the panel is fixed wiring, using Fire resisting 3-core cable
(Between 1 mm² and 2.5mm²) or a suitable 3-conductor system, fed from an isolating
double pole switch fused spur, fused at 3A. IT SHOULD NOT BE CONNECTED
THROUGH AN RCD. This should be secure from unauthorised operation and be
marked 'FIRE ALARM: DO NOT SWITCH OFF'. The supply must be exclusive to the
Fire Panel. MAKE SURE ANY SPARE ENTRY HOLES ARE COVERED WITH THE
GROMMETS PROVIDED

Connecting the batteries

The Premier EX8 requires 2 x 12 V sealed lead acid (SLA) batteries
The two batteries are wired in series.
The +ve of one battery is connected to the red battery lead.
The –ve of the other battery is connected to the black battery lead.
The –ve of the first battery is connected to the +ve of the second battery using the
link wire supplied.
Although there are many sizes of suitable battery, the enclosure has been designed
for 12V 7Ah or 12V 12Ah. Use the battery calculation information later in this manual
to work out the required stand by battery size.

Charger Short Circuit Protection

The Premier EX8 has an intelligent charger that senses if too much current is being
drawn (for instance in the case of totally discharged batteries, or the charger leads
being shorted together). In such an event, the Premier EX8 4-8 zone panel will turn
off the power to its charger circuit.
The panel also turns off the charger when the batteries are disconnected.
PAGE 14
Approved Document No: GLT.MAN-124
Issue : 1
Author: NRPJ
Date: 15/11/2007