Earth Fault; System Fault; Repeater Fault; Remote Fault - Zeta Premier EX8 Instruction Manual

Combined fire & extinguishing control panel ex8, complies with bs en 12094 part 1 and en54 parts 2 & 4
Hide thumbs Also See for Premier EX8:
Table of Contents

Advertisement

Extinguishing Panel - INSTRUCTION MANUAL

Earth Fault

An EARTH fault indicates that something is shorting to earth (usually through the cable screen).
Disconnect the earth screens one at a time to determine the problem line.
(Note: connecting other equipment , eg an oscilloscope or PC, to the panel can give an earth fault)
The voltage between battery –Ve and earth should be 14-16 volts. If it is not, the voltage should
indicate what is shorting to earth.

System Fault

A system fault is an abnormal microprocessor running condition due to various unexpected
phenomena.
This will result in the panel attempting to correct itself. Should this fault occur, the System Fault LED,
General Fault LED, General Fault relay and fault internal buzzer will be constantly active until the
control keyswitch is turned from off position to control enable position. This should cause this fault
condition to reset. If not, consult your supplier.

Repeater fault

The panel can no longer communicate with the repeater (check that the cables are intact, and that the
fuse in the repeater, and the panel`s serial supply line are intact. If the system does not have a
repeater, then the monitoring link has been incorrectly fitted.

Remote Fault

The panel has received a signal on it`s remote fault input. Check any items connected to this input.
PAGE 24
Approved Document No: GLT.MAN-124
Issue : 1
Author: NRPJ
Date: 15/11/2007