Quarterly Test (to be carried out by authorised service personnel only)
Check that any servicing or repairs required by all previous logbook entries has been
undertaken.
Visual inspection of the batteries and connections. Check the alarm sounders work on battery
only.
Activate a device from each zone to test the fire alarm. (As per weekly test).
Annual Test (to be carried out by authorised service personnel only)
Check every detector, call point, sounder and all auxiliary equipment for correct operation.
Check Cage output Voltage (29.5VDC), Charger Voltage (27.6Vnormal) & Battery Voltage (25-
27V)
Every Five Years (to be carried out by authorised service personnel only)
Carry out a complete wiring check in accordance with the testing and inspection requirements
of the relevant National wiring regulations (in the UK this is the IEE Wiring Regulations). The
Batteries should be replaced because SLA batteries have a working life of 5 years.