Zeta Premier EX8 Instruction Manual page 6

Combined fire & extinguishing control panel ex8, complies with bs en 12094 part 1 and en54 parts 2 & 4
Hide thumbs Also See for Premier EX8:
Table of Contents

Advertisement

Extinguishing Panel - INSTRUCTION MANUAL
The Premier EX8 has the following LED indicators:-
LED
POWER
COMMON FIRE
COMMON FAULT
BATTERY FAULT
CHARGER FAULT
LOW BATTERY
EARTH FAULT
EXT.FAN DISABLE
SYSTEM FAULT
REMOTE FAULT
REPEATER FAULT
GEN S/C FAULT
EXTINGUISHANT RELEASED
RELEASE IMMINENT
HOLD/ABORT
MANUAL RELEASE
S T
1
STAGE ALARM
N D
2
STAGE ALARM
LOW PRESSURE
FLOODING ZONE FAULT
MANUAL MODE
AUTOMATIC MODE
GENERAL DISABLEMENT
GENERAL TEST
CONTROLS ACTIVE
ZONE 1-6 FIRE
ZONE 1-6 FAULT
ZONE 1-6 TEST
ZONE 1-6 DISABLED
S T
1
STAGE SNDR ACTIVE
S T
1
STAGE SNDR FAULT
S T
1
STAGE SNDR TEST
S T
1
STAGE SNDR DISABLED
N D
2
STAGE SNDR ACTIVE
N D
2
STAGE SNDR FAULT
N D
2
STAGE SNDR TEST
N D
2
STAGE SNDR DISABLED
BOTTLE OUTPUT ACTIVE
BOTTLE OUTPUT FAULT
BOTTLE OUTPUT TEST
BOTTLE OUTPUT DISABLED
S T
1
STAGE RELAY ACTIVE
S T
1
STAGE RELAY TEST
S T
1
STAGE RELAY DISABLED
N D
2
STAGE RELAY ACTIVE
N D
2
STAGE RELAY TEST
N D
2
STAGE RELAY DISABLED
MAN.L RELEASE INPUT ACTIVE
MAN. RELEASE INPUT FAULT
MAN. RELEASE INPUT DISABLED
GAS FIRED INPUT ACTIVE
GAS FIRED INPUT FAULT
GAS FIRED INPUT DISABLED
EMERG. HOLD INPUT ACTIVE
EMERG. HOLD INPUT FAULT
EMERG. HOLD INPUT DISABLED
EMERG. ABORT INPUT ACTIVE
EMERG. ABORT INPUT FAULT
EMERG. ABORT INPUT DISABLED
AUTO/MANUAL INPUT ACTIVE
AUTO/MANUAL INPUT FAULT
AUTO/MANUAL INPUT DISABLED
PRESS. SWITCH INPUT ACTIVE
PRESS. SWITCH INPUT FAULT
PRESS. SWITCH INPUT DISABLED
BOTTLE SCALES INPUT ACTIVE
BOTTLE SCALES INPUT FAULT
BOTTLE SCALES INPUT DISABLED
ACCESS LEVEL 3
GAS RELEASE COUNTER
RELEASE DURATION TIME
RESET INHIBIT TIME
Approved Document No: GLT.MAN-124
Issue : 1
Author: NRPJ
COLOUR
FUNCTION / MEANING
GREEN
The panel is supplied with power, either battery, mains or both
RED
There is an alarm on the system. Check which zone caused the alarm
YELLOW
There is a fault on the system. Another LED(s) will be lit to indicate the specific fault
YELLOW
There is a problem with the batteries. Rectify or replace.
YELLOW
The panel is not charging the batteries (usually mains fail or low mains)
YELLOW
The batteries are below their final voltage & should be replaced
YELLOW
Problem in system wiring. At least one cable is shorting to earth.
YELLOW
The external equipment relay has been disabled
YELLOW
The CPU has crashed, (Or CPU reset has been pressed & held)
YELLOW
The panel has received a fault input from external equipment
YELLOW
The panel has lost communication with the repeater panel
YELLOW
Indicated that a line fault is caused by a short circuit
RED
The bottle output has been activated & the gas released
RED
The panel has started the release timer and will activate bottle imminently
GREEN
An emergency hold OR emergency abort input has been activated.
RED
A manual release call point has been activated
RED
One of the crossed zones is in alarm
RED
Both of the crossed zones are in alarm
YELLOW
A drop in bottle pressure has been detected
YELLOW
There is a fault relating to the flooding zone1
YELLOW
The panel is in manual only mode (ie will not be triggered by detectors)
GREEN
The panel is in automatic or manual mode
YELLOW
Lights when any section of the system is disabled
YELLOW
Lights when any section of the panel is in test mode
YELLOW
Lights when controls enabled keyswitch is on
RED
Lights when one of the detection zones is in alarm
YELLOW
Lights when one of the detection zones has a fault
YELLOW
Lights when one of the detection zones is in test mode
YELLOW
Lights when one of the detection zones is in disablement mode
RED
Lights when the first stage sounder is on
YELLOW
Lights when the first stage sounder has a wiring fault
YELLOW
Lights when the first stage sounder is in test mode
YELLOW
Lights when the first stage sounder is disabled
RED
Lights when the second stage sounder is on
YELLOW
Lights when the second stage sounder has a wiring fault
YELLOW
Lights when the second stage sounder is in test mode
YELLOW
Lights when the second stage sounder is disabled
RED
Lights when the bottle output is on
YELLOW
Lights when the bottle output has a wiring fault
YELLOW
Lights when the bottle output is in test mode
YELLOW
Lights when the bottle output is disabled
RED
Lights when the first stage relay is on
YELLOW
Lights when the first stage relay is in test mode
YELLOW
Lights when the first stage relay is disabled
RED
Lights when the second stage relay is on
YELLOW
Lights when the second stage relay is in test mode
YELLOW
Lights when the second stage relay is disabled
RED
A manual release call point connected to the remote input has been activated
YELLOW
Fault in wiring to Manual release call point
YELLOW
Manual release remote input has been disabled
RED
The panel has received a signal from the cylinder to say the gas has been released.
YELLOW
There is a wiring fault to the bottle`s sensor
YELLOW
The Gas fired remote input has been disabled.
RED
The emergency hold input has been activated
YELLOW
Fault in wiring to Emergency hold switch
YELLOW
The emergency hold input has been disabled
RED
The emergency abort input has been activated
YELLOW
Fault in wiring to Emergency abort switch
YELLOW
The emergency abort input has been disabled
RED
The panel has been set to manual mode by a remote input
YELLOW
Fault in wiring to Auto / Manual switch
YELLOW
The Auto / Manual remote input has been disabled.
RED
The bottle`s pressure switch output has been activated
YELLOW
Fault in wiring to bottle`s pressure switch
YELLOW
The pressure switch input has been disabled
RED
The bottle`s scales switch has been activated
YELLOW
Fault in wiring to bottle`s scales switch
YELLOW
The bottle`s scales iinput has been disabled
YELLOW
Access level 3 selected
YELLOW
Gas release counter is being displayed on 3 digit display
YELLOW
Release duration time is being displayed on 3 digit display
YELLOW
Reset inhibit time is being displayed on 3 digit display
Date: 15/11/2007
PAGE 6