Extinguishing Panel - INSTRUCTION MANUAL

Bottle Scales Input

This input connects to an Emergency Abort Switch or call point. The line needs a 2k2
end of line resistor, and a 470R resistor across the line to trigger it.
This is an ancillary bottle connection. If the bottle has only a bottle scales to indicate
the release of the gas, it should be connected to the GAS FIRED input. If the bottle
has more than one input, connect the primary indication to GAS FIRED, and the
secondary indication can be connected to the bottle scales input.
There is a RED "ACTIVE " LED which lights when the input has been operated, and
a yellow fault LED that lights in the event of an O/C or S/C line fault.
Disabling this input prevents it from showing as active on the panel display.

USING THE REMOTE CONTROL INPUTS

The Premier EX8 has remote control inputs for Start/Stop Sounders, Silence Buzzer, Reset
and Remote fault.
They are operated by connecting the signal to 0V. The first 3 will mimic pressing the button
on the front panel. The Fault input is used to receive a fault signal from external equipment
(eg an add on power supply). If this input is operated it will operate the panel`s fault relay.
These inputs can be connected to key controlled switches, or Output modules on an
addressable fire alarm system. Remember to heed local fire fighting regulations when using
remote inputs.
The remote inputs to not prevent the panel buttons from functioning.
PAGE 12
Approved Document No: GLT.MAN-124
Issue : 1
Author: NRPJ
Date: 15/11/2007