Factory Test Record - Zeta Premier EX8 Instruction Manual

Combined fire & extinguishing control panel ex8, complies with bs en 12094 part 1 and en54 parts 2 & 4
Hide thumbs Also See for Premier EX8:
Table of Contents

Advertisement

Extinguishing Panel - INSTRUCTION MANUAL

Factory Test Record

Initial Setup
1. Turn on MAINS (panel shows Battery fault)
2. Set Battery charger voltage to 28.4V DC
3. Check Panel 5V rail is between 4.9 & 5.1V DC
4. Check Zone Voltage is between 18 & 20V DC
5. Connect Battery & check for Quiescent state.
Zone Status Check
(Panel is returned to quiescent after every test)
TEST
Z1 O/C
Z1 S/C
Z1 FIRE
Z2 O/C
Z2 S/C
Z2 FIRE
Z3 O/C
Z3 S/C
Z3 FIRE
Z4 O/C
Z4 S/C
Z4 FIRE
Z5 O/C
Z5 S/C
Z5 FIRE
Z6 O/C
Z6 S/C
Z6 FIRE
Crossed Zones Test
(The 2 crossed zones are both set into alarm, and the outputs recorded)
Event
Zone 1 ALARM
Zone 2 ALARM
Wait timer 1
Wait timer 2
Gas Rel. Input
Wait timer 3
Reset
Approved Document No: GLT.MAN-124
Issue : 1
Author: NRPJ
Date: 15/11/2007
Panel serial No
PCB Version
Build List Version
Software Version
DVM Serial Number
PAGE 31