Bottle Output; External Equipment Relay - Zeta Premier EXPro Installation Manual

Hide thumbs Also See for Premier EXPro:
Table of Contents

Advertisement

EXPro Installation Manual

BOTTLE OUTPUT

The bottle output on the Premier EXPRO is used to drive a gas release solenoid. It is fused @ 1amp.
Bottle +
Bottle -
Figure 8. Wiring diagram for the solenoid valve (Bottle output)

EXTERNAL EQUIPMENT RELAY

The Premier EXPRO has one volt free change over relay that operates AFTER the reset inhibit
counter has finished. It remains active for the time preset through the timers menu (default 2.5
minutes), or until the reset button is pressed. It is rated at 1amp, SELV. This would normally be used
for a ventilation fan.
Approved Document No: GLT-212-7-1
Issue: 1.7 Author: MF/NRPJ Date: 05/07/2021
www.acornfiresecurity.com
Solenoid Valve
+ +
- -
www.acornfiresecurity.com