Autoping Commands
get autoping
set autoping <1a | 1b | 2 | 3> ipaddress
<dotted decimal>
set autoping <1a | 1b | 2 | 3> frequency
<1-999>
set autoping <1a | 1b | 2 | 3> failcount <1-
999>
set autoping 1 logic <a | and | or>
Set autoping <1 | 2 | 3> outlet <main |
exp1 | exp2>
set autoping <1 | 2 | 3> action <none | on-
latch | on-follow | off-latch | off-follow |
cycle>
set autoping <1 | 2 | 3> cycle <0-999>
set autoping <1 | 2 | 3> wait <1-999>
V130108E
These commands require a reboot before they will take effect.
These commands are available to the administrator only.
This command returns all of the AutoPing settings as shown below.
Autoping 1   A                B              Status   Trigger Count 
IP Address:  123.12.123.12    0.0.0.0        OK       0 
Frequency:   1                10 
Fail Count:  1                3 
Logic:       A And B 
Action:      None 
Cycle:       1 
Outlet:      Main 
Wait:        2 
 
Autoping 2                                   Status   Trigger Count 
IP Address:  0.0.0.0                         OK       0 
Frequency:   10 
Fail Count:  3 
Action:      None 
Cycle:       1 
Outlet:      Exp1 
Wait:        2 
 
Autoping 3                                   Status   Trigger Count 
IP Address:  0.0.0.0                         OK       0 
Frequency:   10 
Fail Count:  3 
Action:      None 
Cycle:       1 
Outlet:      Exp2 
Wait:        2
This command is used to set the IP address of
AutoPing 1 or AutoPing 2
This command is used to set the frequency, in
seconds (how often the iBoot-G2+ sends the ping) for
each of the AutoPings.
This command is used to set the number of
consecutive failures the AutoPings must detect before
the AutoPing considers the pinged device to be failed.
Sets logic for AutoPing 1. A = A Only, and = A and B,
or = A or B.
This command sets the outlet that the AutoPing will
trigger.
This command is used to set the action that the iBoot-
G2+ will perform when the AutoPing triggers.
This command sets the maximum number of power
cycles when the AutoPing triggers. 0 = Unlimited
This command sets the time, in seconds for the device
to respond to a ping.
iBoot-G2+
0.0.0.0
10
3
A and B
Main
None
1
2
Page 28