588A048,060 With Optional Base Rail, Unit Dimensions - Bryant 588A Installation, Start-Up And Service Instructions Manual

Single package gas heating/ electric cooling units
Hide thumbs Also See for 588A:
Table of Contents

Advertisement

UNIT
588A
048080
208/230-1-60, 208/230-3-60, 460-3-60
048100/120/140
208/230-1-60, 208/230-3-60, 460-3-60
060080
208/230-1-60, 208/230-3-60, 460-3-60
060100/120/140
208/230-1-60, 208/230-3-60, 460-3-60
CENTER OF GRAVITY (in./mm)
UNIT
588A
X
048080
28.54/724.9
048100/120/140
28.22/716.8
060080
28.18/715.6
060100/120/140
27.79/705.9
ELECTRICAL
CHARACTERISTICS
Y
Z
20.00/508
17.66/448.6
20.05/509.3
17.66/448.6
20.19/512.8
17.66/448.6
20.23/513.8
17.66/448.6
Fig. 5 — 588A048,060 With Optional Base Rail, Unit Dimensions
REQ'D CLEARANCES FOR SERVICING. in. (mm)
Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side opposite ducts
. . . . . . . . . . . . . . . . . . . . . 36 (914)
Compressor access
. . . . . . . . . . . . . . . . . . . . . 36 (914)
(Except for NEC requirements)
REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)
Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)
Side opposite ducts
. . . . . . . . . . . . . . . . . . . . . 14 (356)
Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Flue panel
. . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
NEC REQ'D CLEARANCES. in. (mm)
Between units, control box side . . . . . . . . . . . . . . . . 42 (1067)
Unit and ungrounded surfaces, control box side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side . . . . . . . . . . . . . . . . . . 42 (1067)
UNIT WEIGHT
lb
kg
A
438
199
113/51
450
205
116/53
477
217
123/56
489
222
126/57
CG
— Center of Gravity
COND — Condenser
LV
— Low Voltage
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-
fan discharge.
2. Adequate clearance around air openings into combustion chamber must
be provided.
—5—
CORNER WEIGHT
(lb/kg)
B
C
89/40
164/75
92/42
165/75
99/45
173/79
102/46
173/79
LEGEND
MAT'L — Material
NEC
— National Electrical Code
REQ'D — Required
D
72/33
77/35
82/37
88/40