589A024-036 Without Base Rail, Unit Dimensions - Bryant 588A Installation, Start-Up And Service Instructions Manual

Single package gas heating/ electric cooling units
Hide thumbs Also See for 588A:
Table of Contents

Advertisement

UNIT
ELECTRICAL
589A
CHARACTERISTICS
024040
208/230-1-60
024060
208/230-1-60
030040
208/230-1-60
030060/080
208/230-1-60
036060/080
208/230-1-60, 208/230-3-60, 460-3-60
036100/120
208/230-1-60, 208/230-3-60, 460-3-60
CENTER OF GRAVITY (in./mm)
UNIT
589A
X
024040
26.71/678
024060
26.64/677
030040
27.06/687
030060/080
26.98/685
036060/080
27.14/689
036100/120
27.06/687
UNIT WEIGHT
lb
kg
333
151
345
157
336
153
348
158
366
166
378
172
Y
Z
20.06/510
12.65/321
20.12/511
12.65/321
21.05/535
12.65/321
21.07/535
12.65/321
21.10/536
12.65/321
21.12/536
12.65/321
Fig. 6 — 589A024-036 Without Base Rail, Unit Dimensions
REQ'D CLEARANCES FOR SERVICING. in. (mm)
Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side opposite ducts
. . . . . . . . . . . . . . . . . . . . . 36 (914)
Compressor access
. . . . . . . . . . . . . . . . . . . . . 36 (914)
(Except for NEC requirements)
REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)
Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)
Side opposite ducts
. . . . . . . . . . . . . . . . . . . . . 14 (356)
Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Flue panel
. . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
NEC REQ'D CLEARANCES. in. (mm)
Between units, control box side . . . . . . . . . . . . . . . . 42 (1067)
Unit and ungrounded surfaces, control box side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side . . . . . . . . . . . . . . . . . . 42 (1067)
CORNER WEIGHT
(lb/kg)
A
B
C
104/47
50/23
130/59
107/49
53/24
133/60
97/44
66/30
118/54
100/45
69/31
121/55
94/43
84/38
117/53
97/44
87/40
120/55
CG
— Center of Gravity
COND — Condenser
LV
— Low Voltage
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-
fan discharge.
2. Adequate clearance around air openings into combustion chamber must
be provided.
—6—
D
49/22
52/24
55/25
58/26
71/32
74/34
LEGEND
MAT'L — Material
NEC
— National Electrical Code
REQ'D — Required