588A018-042 With Optional Base Rail, Unit Dimensions - Bryant 588A Installation, Start-Up And Service Instructions Manual

Single package gas heating/ electric cooling units
Hide thumbs Also See for 588A:
Table of Contents

Advertisement

REQ'D CLEARANCES FOR SERVICING. in. (mm)
Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side opposite ducts
. . . . . . . . . . . . . . . . . . . . . 36 (914)
Compressor access
. . . . . . . . . . . . . . . . . . . . . 36 (914)
(Except for NEC requirements)
REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)
Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)
Side opposite ducts
. . . . . . . . . . . . . . . . . . . . . 14 (356)
Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Flue panel
. . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
NEC REQ'D CLEARANCES. in. (mm)
Between units, control box side . . . . . . . . . . . . . . . . 42 (1067)
Unit and ungrounded surfaces, control box side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side . . . . . . . . . . . . . . . . . . 42 (1067)
UNIT
ELECTRICAL
588A
CHARACTERISTICS
018040
024040
024060
030040
208/230-1-60, 208/230-3-60
030060/080
208/230-1-60, 208/230-3-60
036060/080
208/230-1-60, 208/230-3-60, 460-3-60
036100/120
208/230-1-60, 208/230-3-60, 460-3-60
042060/080
208/230-1-60, 208/230-3-60, 460-3-60
042100/120
208/230-1-60, 208/230-3-60, 460-3-60
UNIT
F
G
588A
in./mm
in./mm
018040
024040
024060
030040
19
/504.8
22
7
1
8
4
030060/080
036060/080
036100/120
042060/080
23
7
/606.4
26
1
8
4
042100/120
208/230-1-60
296
208/230-1-60
327
208/230-1-60
339
344
356
360
372
399
411
CENTER OF GRAVITY in./mm
X
Y
25.04/636
22.72/577
26.90/683.3
20.17/512.3
26.82/681.2
20.22/513.6
/565.4
26.57/674.9
20.1 /509.3
26.93/684
21.1 /535.4
27.31/693.7
21.0 /532.6
27.23/691.6
21.0 /533.1
26.87/682.5
21.0 /533.1
/666.8
26.81/681
21.0 /533.7
Fig. 3 — 588A018-042 With Optional Base Rail, Unit Dimensions
UNIT WEIGHT
lb
kg
A
135
87/40
149
103/47
155
106/48
157
106/48
162
102/46
164
92/42
169
95/43
181
101/46
187
104/47
CG
— Center of Gravity
Z
COND — Condenser
LV
— Low Voltage
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-
13.16/334.3
fan discharge.
2. Adequate clearance around air openings into combustion chamber must
be provided.
14.96/380
—3—
CORNER WEIGHT
(lb/kg)
B
C
D
68/31
82/37
59/27
49/22
129/59
46/21
52/24
132/60
49/22
53/24
132/60
53/24
71/32
123/56
60/27
82/37
117/53
69/31
85/39
120/55
72/33
92/42
125/57
81/37
95/43
128/58
84/38
LEGEND
MAT'L — Material
NEC
— National Electrical Code
REQ'D — Required
UNIT HEIGHT
(in./mm)
E
27.4/697
27.4/697
27.4/697
27.4/697
27.4/697
27.4/697
27.4/697
31.4/798
31.4/798

Hide quick links: