W7220 Economizer Module Wiring; Time-Out And Screen Saver; Start-Up And Operation; Cooling, Unit With Economi$Er® X - Bryant 582K Installation Instructions Manual

3 to 12.5 tons (48/50lc 14 not included) accessory ultra low leak vertical economiser x
Hide thumbs Also See for 582K:
Table of Contents

Advertisement

W7220 Economizer Module Wiring

Use Tables 12 and 13 to locate the wiring terminals for the
economizer module.
Table 12 — Economizer Module - Left Hand Terminal
LABEL
TYPE
Top Left Terminal Block
20k NTC
Mixed Air Temperature Sensor (Polarity
MAT
and COM
Insensitive Connection)
20k NTC
Outdoor Air Temperature Sensor (Polarity
OAT
and COM
Insensitive Connection)
S-BUS (Sylk
Enthalpy Control Sensor
S-BUS
Bus)
(Polarity Insensitive Connection)
Bottom Left Terminal Block
Air Quality Sensor Input (e.g. CO
IAQ 2-10
2-10 vdc
sensor)
IAQ COM
COM
Air Quality Sensor Common
IAQ 24V
24 vac
Air Quality Sensor 24 vac Source
ACT 2-10
2-10 vdc
Damper Actuator Output (2-10 vdc)
ACT COM
COM
Damper Actuator Output Common
ACT 24v
24 vac
Damper Actuator 24 vac Source
Table 13 — Economizer Module - Right Hand
Terminal Blocks
LABEL
TYPE
Top Right Terminal Blocks
The first terminal is not used.
na
Shut Down (SD) or HEAT (W)
Conventional only
AUX2 I
24 vac IN
and
Heat Pump Changeover (O-B) in Heat
Pump mode.
OCC
24 vac IN
Occupied/Unoccupied Input
E-GND
E-GND
Earth Ground - System Required
EXH1
24 vac OUT
Exhaust Fan 1 Output
Programmable:
Exhaust fan 2 output
or
AUX1 O
24 vac OUT
ERV
or
System alarm output
Bottom Right Terminal Blocks
Y2 in - Cooling Stage 2 Input from space
Y2-I
24 vac IN
thermostat
Y2 out - Cooling Stage 2 Output to stage
Y2-O
24 vac OUT
2 mechanical cooling
Y1 in - Cooling Stage 2 Input from space
Y1-I
24 vac IN
thermostat
Y1 out - Cooling Stage 2 Output to stage
Y1-O
24 vac OUT
2 mechanical cooling
C
COM
24 vac Common
R
24 vac
24 vac Power (hot)

Time-out and Screen Saver

When no buttons have been pressed for 10 minutes, the LCD
displays a screen saver, which cycles through the Status items.
Each status item displays in turn and cycles to the next item after
5 seconds.
Blocks
DESCRIPTION
DESCRIPTION

START-UP AND OPERATION

Cooling, Unit with EconoMi$er
For Occupied mode operation of EconoMi$er X system, there
must be a 24-v signal at terminals R and OCC (provided through
PL6-3 from the unit's IFC coil). Removing the signal at OCC
places the EconoMi$er X control in Unoccupied mode. See
Table 14 for Damper Position Control.
During Occupied mode operation, indoor fan operation will be
accompanied by economizer dampers moving to Minimum
Position setpoint for ventilation. If indoor fan is off, dampers will
close. During Unoccupied mode operation, dampers will remain
closed unless a Cooling (by free cooling) or DCV demand is
received.
When free cooling using outside air is not available, the unit
cooling sequence will be controlled directly by the space
thermostat. Outside air damper position will be closed or
2
Minimum Position as determined by Occupancy mode and fan
signal.
When free cooling is available as determined by the appropriate
changeover command (dry bulb, outdoor enthalpy, differential dry
bulb or differential enthalpy), a call for cooling (Y1 closes at the
thermostat) will cause the economizer control to modulate the
dampers open and closed to maintain the unit supply air
temperature. Default mixed air temperature is 53°F, with a range
of 38°F to 70°F. Compressor will not run.
Should 100% outside air not be capable of satisfying the space
temperature, space temperature will rise until Y2 is closed. The
economizer control will call for compressor operation. Dampers
will modulate to maintain MAT at set point concurrent with
Compressor 1 operation. The "Low T Lock" setting (default 32°F)
will lock out compressor operation when outside air temperature
is below setpoint.
When space temperature demand is satisfied (thermostat Y1
opens), the dampers will return to Minimum Damper position if
indoor fan is running or fully closed if fan is off.
If accessory power exhaust is installed, the power exhaust fan mo-
tors will be energized by the economizer control as the dampers
open above the EXH1 SET setpoint and will be de-energized as
the dampers close below the EXH1 SET setpoint. (For single
speed unit.)
Damper movement from full closed to full open (or vice versa)
will take between 1-1/2 and 2-1/2 minutes.
Heating with EconoMi$er
During Occupied mode operation, indoor fan operation will be
accompanied by economizer dampers moving to Minimum
Position setpoint for ventilation. If indoor fan is off, dampers
will close. During Unoccupied mode operation, dampers will
remain closed unless a DCV demand is received.
When the room temperature calls for heat (W1 closes), the heating
controls are energized.
22
X
®
X
®

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents