Bryant 580J***(D Submittal Data

Single package rooftop gas heating/electric cooling unit two stage cooling capacity control with novation coil sizes 08, 12, 14 with puron (r--410a) refrigerant
Hide thumbs Also See for 580J***(D:

Advertisement

580J***(D,F)
SINGLE PACKAGE ROOFTOP
GAS HEATING/ELECTRIC COOLING UNIT
TWO STAGE COOLING CAPACITY CONTROL WITH NOVATIONt COIL
SIZES 08, 12, 14 WITH PURONR (R- - 410A) REFRIGERANT
®
This product has been designed and manufactured
to meet Energy Star® criteria for energy efficiency.
However, proper refrigerant charge and proper air
flow are critical to achieve rated capacity and effi-
ciency. Installation of this product should follow all
manufacturer's refrigerant charging and air flow in-
structions. Failure to confirm proper charge and
air flow may reduce energy efficiency and short-
en equipment life.
Base Unit
S Puron (R- -410A) HFC refrigerant
S ARI certified efficiency levels up to 11.1 EER
S Rated in accordance with ARI Standard 360
S Designed in accordance with Underwriters' Laboratories Std
1995 and listed by UL and UL, Canada
S Two- -stage cooling capacity control
S Non- -corrosive composite sloping design; side or center drain
condensate pan. Meets ASHRAE Standard 62
S Standard cooling operating range from 40_F up to 115_F
(4_C up to 46_C). Field installable accessory extends the
minimum down to - -20_F (- -29_C).
S Convertible from vertical to horizontal airflow for slab mounting
S Two- -inch disposable return air filters
S Thru- -the- -bottom power and gas entry capability
S Single point gas and electric connections
S 24- -volt control circuit protected with resettable circuit breaker
and 75- -VA transformer
S Belt drive, constant torque, permanently lubricated
evaporator–fan motor
S Totally enclosed condenser motors with permanently lubricated
bearings
S Low- -pressure and high- -pressure switches
S Full perimeter base rail with built- -in rigging adapters and fork
truck slots
S Centralized Terminal Board for component and unit wiring
connections
Submittal Data
580J***(D,F) units are high- - efficiency, single- - packaged
electric cooling, gas heating units that are pre- - wired and
pre- - charged with PuronR (R- - 410A) HFC refrigerant.
Units utilize an all aluminum flat micro- - channel tube
with louvered fins condenser coil—NOVATIONt. The
units are factory tested in both heating and cooling modes.
These units meet the ASHRAE 90.1- - 2007 and Energy
Star minimum efficiency levels as well as also meeting
2010 efficiency standards.
STANDARD FEATURES
Cabinet
S Access panels with easy grip handles and NO- -STRIP screw
collar
S Pre- -painted exterior panels and primer- -coated interior panels
tested to 500 hours salt spray protection
S Fully insulated cabinet
S Tool- -less filter access door
Refrigerant System
S Acutrolt refrigerant metering system
S Liquid line filter drier
S Scroll compressors with internal line- -break overload protection
S Copper
S NOVATION all aluminum condenser coil
S Removable gauge line plugs for reading refrigerant pressure
with unit panels in place

Gas Heat

S IGC solid- -state gas heat exchanger control for on- -board
diagnostics, anti- -cycle protection, LED error code designation,
burner control logic and energy saving indoor fan motor delay
S Gas efficiencies up to 82%
S Designed in accordance with ANSI Z21.47 (design and test
standard for gas furnaces) and ANSI Z233.1 (National Fuel Gas
code relating to appliance installation requirements)
S Induced draft combustion
S Redundant gas valve, with up to 2 stages of heating
S Flame roll- -out safety protector
S Solid- -state electronic direct spark ignition system
DESCRIPTION
tube
, aluminum fin evaporator coil

Advertisement

Table of Contents
loading

Summary of Contents for Bryant 580J***(D

  • Page 1: Gas Heat

    S Centralized Terminal Board for component and unit wiring connections Submittal Data 580J***(D,F) units are high- - efficiency, single- - packaged electric cooling, gas heating units that are pre- - wired and pre- - charged with PuronR (R- - 410A) HFC refrigerant.
  • Page 2: Performance Data

    STANDARD FEATURES (cont.) Standard Warranty S 15- -year gas heat exchanger - - Stainless Steel S 10- -year gas heat exchanger - - Aluminized S 5- -year compressor S 3- -year NOVATION condenser coil S 1- -year parts Job Name Architect Engineer Contractor...
  • Page 3: Options And Accessories

    OPTIONS AND ACCESSORIES FACTORY- -INSTALLED OPTIONS (FIOPs) j Open protocol RTU- - MP controller communicates to LON, MODBUS, BACNET and Johnson N2 protocols. j Through the base connectors for gas and electric conduit/piping j Stainless steel gas heat exchanger (includes tubes, vestibule plate and collector box) j Economizer with dry bulb sensing and barometric relief...
  • Page 8: Roof Curb Details

    CRRFCURB004A01 (610) E2008 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. ROOF CURB DETAILS...

This manual is also suitable for:

F)580j series 580j***d series580j***f series