Bryant 588A Installation, Start-Up And Service Instructions Manual

Bryant 588A Installation, Start-Up And Service Instructions Manual

Single package gas heating/ electric cooling units
Hide thumbs Also See for 588A:
Table of Contents

Advertisement

CONTENTS

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . 1

General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Receiving And Installation . . . . . . . . . . . . . . . . . 10-22
I. Step 1 — Check Equipment . . . . . . . . . . . . . . . . . 10
II. Step 2 — Provide Unit Support . . . . . . . . . . . . . . 10
III. Step 3 — Field Fabricate Ductwork . . . . . . . . . . . 10
IV. Step 4 — Provide Clearances . . . . . . . . . . . . . . . . 10
V. Step 5 — Rig and Place Unit . . . . . . . . . . . . . . . . 10
VI. Step 6 — Connect Condensate Drain . . . . . . . . . 13
VII. Step 7 — Install Flue Hood . . . . . . . . . . . . . . . . . . 13
VIII. Step 8 — Install Gas Piping . . . . . . . . . . . . . . . . . 13
IX. Step 9 — Install Duct Connections . . . . . . . . . . . 16
X. Step 10 — Install Electrical Connections . . . . . . 18
Pre-Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22,23
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23-44
I. Check for Refrigerant Leaks . . . . . . . . . . . . . . . . . 23
II. Start Up Heating Section and
Make Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . 23
III. Start Up Cooling Section and
Make Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . 26
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44-47
I. Air Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
II. Unit Top Removal . . . . . . . . . . . . . . . . . . . . . . . . . . 45
III. Evaporator Blower and Motor . . . . . . . . . . . . . . . . 45
IV. Flue Gas Passageways . . . . . . . . . . . . . . . . . . . . . 45
V. Combustion-Air Blower . . . . . . . . . . . . . . . . . . . . . 46
VI. Limit Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
VII. Burner Ignition . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
VIII. Main Burners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
IX. Condenser Coil, Evaporator Coil, and
Condensate Drain Pan . . . . . . . . . . . . . . . . . . . . . . 47
X. Condenser Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
XI. Electrical Controls and Wiring . . . . . . . . . . . . . . . 47
XII. Refrigerant Circuit . . . . . . . . . . . . . . . . . . . . . . . . . 47
XIII. Gas Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
XIV. Evaporator Airflow . . . . . . . . . . . . . . . . . . . . . . . . . 47
XV. Metering Device — Acutrol™ Device . . . . . . . . . . 47
XVI. Liquid Line Strainer . . . . . . . . . . . . . . . . . . . . . . . . 47
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . 48-50
Start-Up Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1
NOTE TO INSTALLER — Before the installation, READ
THESE INSTRUCTIONS CAREFULLY AND COMPLETELY.
Also, make sure the User's Manual and Replacement Guide
are left with the unit after installation. This unit is NOT to
be used for temporary heating of buildings or structures un-
der construction.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified personnel should install,
repair, or service air-conditioning equipment.
installation, start-up
and service instructions
SINGLE PACKAGE GAS HEATING/
ELECTRIC COOLING UNITS
Page
Cancels: II 588A-18-8
Fig. 1 — Unit 589A Shown With Optional Base Rail
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters. All other operations should
be performed by trained service personnel. When working on
air-conditioning equipment, observe precautions in the lit-
erature, tags and labels attached to the unit, and other safety
precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire ex-
tinguisher available for all brazing operations.
WARNING: Improper installation, adjustment, alter-
ation, service, maintenance, or use can cause carbon mon-
oxide poisoning, fire, or an explosion which can result
in personal injury or unit damage. Consult a qualified
installer, service agency, or gas supplier for informa-
tion or assistance. The qualified installer or agency must
use only factory-authorized kits or accessories when modi-
fying this product.
WARNING: Before performing service or mainte-
nance operations on unit, turn off gas supply then unit
main power switch. Electrical shock could cause per-
sonal injury.
GENERAL
The 588A, 589A units (see Fig. 1) are fully self-contained, com-
bination Category I gas heating/electric cooling units de-
signed for outdoor installation. See Fig. 2-9 (pages 2-9) for
unit dimensions. All unit sizes have discharge openings for
both horizontal and downflow configurations, and are factory
shipped with all 4 duct openings covered. Units may be in-
stalled either on a rooftop or a ground-level cement slab. See
Fig. 10 for roof curb dimensions.
588A
Sizes 018-060
589A
Sizes 024-060
II 588A-18-9
9/15/98

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 588A and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Bryant 588A

  • Page 1 NOTE TO INSTALLER — Before the installation, READ GENERAL THESE INSTRUCTIONS CAREFULLY AND COMPLETELY. The 588A, 589A units (see Fig. 1) are fully self-contained, com- Also, make sure the User’s Manual and Replacement Guide bination Category I gas heating/electric cooling units de- are left with the unit after installation.
  • Page 2 ....42 (1067) CORNER WEIGHT UNIT HEIGHT UNIT WEIGHT UNIT ELECTRICAL (lb/kg) (in./mm) 588A CHARACTERISTICS 018040 208/230-1-60 81/37 62/28 76/35 53/24 24.1/613...
  • Page 3 ....42 (1067) CORNER WEIGHT UNIT HEIGHT UNIT WEIGHT UNIT ELECTRICAL (lb/kg) (in./mm) 588A CHARACTERISTICS 018040 208/230-1-60 87/40 68/31 82/37 59/27 27.4/697...
  • Page 4 ....42 (1067) CORNER WEIGHT UNIT WEIGHT UNIT ELECTRICAL (lb/kg) 588A CHARACTERISTICS 048080 208/230-1-60, 208/230-3-60, 460-3-60 107/49 83/38 158/72...
  • Page 5 ....42 (1067) CORNER WEIGHT UNIT WEIGHT UNIT ELECTRICAL (lb/kg) 588A CHARACTERISTICS 048080 208/230-1-60, 208/230-3-60, 460-3-60 113/51 89/40 164/75...
  • Page 6 REQ’D CLEARANCES FOR SERVICING. in. (mm) Duct panel ......0 Unit top ......36 (914) Side opposite ducts .
  • Page 7 REQ’D CLEARANCES FOR SERVICING. in. (mm) Duct panel ......0 Unit top ......36 (914) Side opposite ducts .
  • Page 8 REQ’D CLEARANCES FOR SERVICING. in. (mm) Duct panel ......0 Unit top ......36 (914) Side opposite ducts .
  • Page 9 REQ’D CLEARANCES FOR SERVICING. in. (mm) Duct panel ......0 Unit top ......36 (914) Side opposite ducts .
  • Page 10: I. Step 1 — Check Equipment

    CGA [Canadian Gas Association] B149 Installation Codes), Check all items against shipping list. Immediately notify your or applicable provisions of local building code. Bryant Heating and Cooling representative if any item is CAUTION: Do not restrict condenser airflow. An air missing.
  • Page 11 PART NUMBER ‘‘A’’ CPRFCURB001A00 8 [203] FLAT CPRFCURB002A00 11 [279] CURB CPRFCURB003A00 14 [356] NOTES: 1. Roof curb must be set up for unit being installed. 2. Seal strip must be applied as required for unit being installed. 3. Dimensions in [ ] are in millimeters. 4.
  • Page 12 Use wood top skid when rigging, to prevent rigging straps from damag- ing unit. Remove 4 screws to slide wood support through rectangular hole in rail. CAUTION: All panels must be in place when rigging. UNIT 588A WEIGHT Fig. 11 — Slab Mounting Details Size 24.4 28.2 22.6...
  • Page 13: Vi. Step 6 — Connect Condensate Drain

    Table 3 and the NFGC for gas pipe sizing. Do not use Model 588A, 589A disposes of condensate water through a ⁄ cast-iron pipe. It is recommended that a black iron pipe is in.
  • Page 14 Table 1 — Physical Data — Unit 588A UNIT SIZE 588A 018040 024040 024060 030040 030060 030080 036060 036080 036100 036120 NOMINAL CAPACITY (ton) ⁄ ⁄ ⁄ ⁄ OPERATING WEIGHT (lb) Without Base Rail With Optional Base Rail COMPRESSORS Rotary...
  • Page 15 Table 2 — Physical Data — Unit 589A UNIT SIZE 589A 024040 024060 030040 030060 030080 036060 036080 036100 036120 NOMINAL CAPACITY (ton) ⁄ ⁄ ⁄ OPERATING WEIGHT (lb) Without Base Rail With Optional Base Rail COMPRESSORS Scroll Quantity REFRIGERANT (R-22) Charge (lb) REFRIGERANT METERING DEVICE Acutrol™...
  • Page 16: Ix. Step 9 — Install Duct Connections

    (Text continued from page 13) A. Configuring Units for Downflow (Vertical) Discharge CAUTION: Unstable operation may occur when the WARNING: Before performing service or mainte- gas valve and manifold assembly are forced out of po- nance operations on the system, turn off main power to sition while connecting improperly-routed rigid gas pip- unit or electrical shock could result.
  • Page 17 Table 3 — Maximum Gas Flow Capacity* NOMINAL LENGTH OF PIPE, FT† INTERNAL IRON PIPE, DIAMETER SIZE (in.) (in.) ⁄ .622 — — ⁄ .824 1.049 ⁄ 1.380 1400 ⁄ 1.610 2100 1460 1180 *Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5-in. wg (based on a 0.60 specific gravity gas).
  • Page 18: X. Step 10 — Install Electrical Connections

    X. STEP 10 — INSTALL ELECTRICAL CONNECTIONS WARNING: The unit cabinet must have an uninter- rupted, unbroken electrical ground to minimize the pos- sibility of personal injury if an electrical fault should occur. This ground may consist of an electrical wire con- nected to the unit ground lug in the control compart- ment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical...
  • Page 19 Table 4A — Electrical Data — Unit 588A VOLTAGE OUTDOOR-FAN INDOOR-FAN UNIT AWG 60 C COMPRESSOR POWER SUPPLY MAX WIRE RANGE MOTOR MOTOR SIZE V-PH-Hz MIN WIRE LENGTH (ft) 588A SIZE MOCP* 208/230-1-60 45.0 12.9 208/230-1-60 12.4 61.0 18.2 208/230-1-60 14.4...
  • Page 20 Table 4B — Electrical Data — Unit 589A VOLTAGE OUTDOOR-FAN INDOOR-FAN UNIT AWG 60 C COMPRESSOR POWER SUPPLY MAX WIRE RANGE MOTOR MOTOR SIZE V-PH-Hz MIN WIRE LENGTH (ft) 589A SIZE MOCP* 208/230-1-60 12.9 62.5 19.5 208/230-1-60 15.0 76.0 22.8 208/230-1-60 16.7 95.0...
  • Page 21 Use no. 18 American Wire Gage (AWG) color-coded, insu- lated (35 C minimum) wires to make the control voltage con- nections between the thermostat and the unit. If the thermo- stat is located more than 100 ft from the unit (as measured along the control voltage wires), use no.
  • Page 22 PRE-START-UP WARNING: Failure to observe the following warn- ings could result in serious personal injury: 1. Follow recognized safety practices and wear protec- tive goggles when checking or servicing refrigerant system. 2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured.
  • Page 23: I. Check For Refrigerant Leaks

    a. Before lighting the unit for the first time, perform II. START UP HEATING SECTION AND MAKE the following: If the gas supply pipe was not purged ADJUSTMENTS before connecting the unit, it will be full of air. It is CAUTION: Complete the required procedures given recommended that the ground joint union be loos- in Pre-Start-Up section on page 22 before starting the...
  • Page 24 †Based on altitudes from sea level to 2000 ft above sea level. For altitudes above 2000 ft: reduce input rating 4% for each additional 1000 ft above 2000 ft. In Canada, from 2000 ft above sea level to 4500 ft above sea level, derate the unit 10%. NOTE: Unit size 018 is 588A only. Measure Gas Flow (Natural Gas Units) Minor adjustment to the gas flow can be made by changing...
  • Page 25 Measure Manifold Pressure (Propane Units) The main burner orifices on a propane gas unit are sized for the unit rated input when the manifold pressure reading matches the level specified in Table 5. Proceed as follows to adjust gas input on a propane gas unit: 1.
  • Page 26: Make Adjustments

    F. Heating Sequence of Operation III. START UP COOLING SECTION AND MAKE ADJUSTMENTS See Fig. 26-33 and unit wiring label. On a call for heating, terminal ‘‘W’’ of the thermostat is en- CAUTION: Complete the required procedures given ergized, starting the induced-draft motor. When the hall- in the Pre-Start-Up section on page 22 before starting effect sensor on the induced-draft motor senses that it has the unit.
  • Page 27 LEGEND — Power — American Wire Gage — Quadruple Terminal — Blower Relay — Contactor — Rollout Switch — Capacitor TRAN — Transformer — Crankcase Heater COMP — Compressor Motor Field Splice — Combustion Relay EQUIP — Equipment Terminal (Marked) —...
  • Page 28 LEGEND — American Wire Gage — Power — Blower Relay — Quadruple Terminal — Contactor — Rollout Switch — Capacitor TRAN — Transformer — Crankcase Heater Field Splice COMP — Compressor Motor — Combustion Relay EQUIP — Equipment Terminal (Marked) —...
  • Page 29 LEGEND — American Wire Gage — Quadruple Terminal — Blower Relay — Rollout Switch — Contactor TRAN — Transformer — Capacitor Field Splice — Crankcase Heater COMP — Compressor Motor — Combustion Relay Terminal (Marked) EQUIP — Equipment — Flame Sensor Terminal (Unmarked) —...
  • Page 30 LEGEND — American Wire Gage — Quadruple Terminal — Blower Relay — Rollout Switch — Contactor — Start Thermistor — Capacitor TRAN — Transformer COMP — Compressor Motor Field Splice — Combustion Relay EQUIP — Equipment — Fuse Link Terminal (Marked) —...
  • Page 31 LEGEND — American Wire Gage — Power — Blower Relay — Quadruple Terminal — Contactor — Rollout Switch — Capacitor — Secondary COMP — Compressor Motor TRAN — Transformer — Combustion Relay Field Splice EQUIP — Equipment — Fuse Link —...
  • Page 32 LEGEND — American Wire Gage — Quadruple Terminal — Blower Relay — Rollout Switch — Contactor TRAN — Transformer — Capacitor Field Splice COMP — Compressor Motor — Combustion Relay EQUIP — Equipment Terminal (Marked) — Fuse Link — Flame Sensor Terminal (Unmarked) —...
  • Page 33 LEGEND — American Wire Gage — Quadruple Terminal — Blower Relay — Rollout Switch — Contactor — Secondary — Capacitor TRAN — Transformer COMP — Compressor Motor Field Splice — Combustion Relay EQUIP — Equipment — Fuse Link Terminal (Marked) —...
  • Page 34 LEGEND — American Wire Gage — Quadruple Terminal — Rollout Switch — Blower Relay — Contactor TRAN — Transformer — Capacitor COMP — Compressor Motor Field Splice — Combustion Relay EQUIP — Equipment Terminal (Marked) — Flame Sensor — Fuse Terminal (Unmarked) —...
  • Page 35 Unit 588A two- or 3-speed motors (except size 030) are fac- tory wired for low speed operation. Unit 588A030 is factory wired for medium speed. Units 589A024,036, and 048 (460 v) two- or 3-speed motors are factory wired for low speed;...
  • Page 36 For Integrated Control Motors (ICM) The selection options allow installer to adjust airflow to meet such individual needs as noise and static compensation, etc. To configure the 589A unit, move the 5 Easy Select board wires to the terminals which control the airflow. Refer to the Easy Select interface board (Fig.
  • Page 37 Table 8C — Superheat Charging Table, 588A030 INDOOR AIR — CFM TEMP (F) 1000 OUTDOOR ENTERING Indoor Air — Ewb (F) 14.2 15.1 16.1 17.1 19.2 21.3 23.3 24.7 25.9 27.2 27.8 28.5 13.6 14.1 14.6 15.0 17.1 19.2 21.3 22.8 24.2 25.7...
  • Page 38 Table 8F — Superheat Charging Table, 588A048 (Carrier Scroll Compressor) INDOOR AIR — CFM TEMP (F) 1600 OUTDOOR ENTERING Indoor Air — Ewb (F) 15.5 15.5 15.6 15.6 17.6 19.6 21.6 22.8 24.0 25.2 25.2 25.3 11.7 11.8 11.8 11.8 13.9 16.0 18.0...
  • Page 39 Table 9A — Superheat Charging Table, 589A024 INDOOR AIR — CFM TEMP (F) OUTDOOR ENTERING Indoor Air — Ewb (F) 22.1 22.1 22.8 23.2 25.3 27.4 29.5 29.8 30.2 30.5 31.3 32.1 18.5 18.9 19.3 19.6 22.2 24.8 27.5 28.3 29.1 30.0 30.0...
  • Page 40 Table 9D — Superheat Charging Table, 589A042 INDOOR AIR — CFM TEMP (F) 1400 OUTDOOR ENTERING Indoor Air — Ewb (F) 23.9 23.9 23.9 23.9 24.4 24.9 25.5 25.8 26.1 26.5 25.6 24.7 21.9 21.9 21.9 21.9 22.4 22.9 23.4 23.7 24.1 24.5...
  • Page 41 82.4 85.7 *Temperature at suction service valve. Table 11 — Dry-Coil Air Delivery* — Horizontal Discharge at 230 and 460 V — Unit 588A (Deduct 10% from Cfm and Watts for 208 V Operation) EXTERNAL STATIC PRESSURE (in. wg) UNIT...
  • Page 42 Table 12 — Dry-Coil Air Delivery* — Downflow Discharge at 230 and 460 V — Unit 588A (Deduct 10% from Cfm and Watts for 208 V Operation) EXTERNAL STATIC PRESSURE (in. wg) UNIT MOTOR 588A SPEED DELIVERY Watts † †...
  • Page 43 Table 14 — Dry-Coil Air Delivery* — Downflow Discharge at 230 and 460 V — Unit 589A (Deduct 10% from Cfm and Watts for 208 V Operation) EXTERNAL STATIC PRESSURE (in. wg) UNIT MOTOR 589A SPEED DELIVERY Watts † † †...
  • Page 44 3. Never place anything combustible either on, or in con- 2300 0.123 tact with, the unit. *Unit 588A only. 4. Should overheating occur, or the gas supply fail to D. Cooling Sequence of Operation shut off, shut off the external main manual gas valve With the room thermostat SYSTEM switch in the COOL po- to the unit, then shut off the electrical supply.
  • Page 45: I. Air Filter

    I. AIR FILTER housing, and slide motor and motor mount out of housing. CAUTION: Never operate the unit without a suit- 2. Lubricate motor as follows: able air filter in the return-air duct system. Always re- a. Thoroughly clean all accumulations of dirt or grease place the filter with the same dimensional size and type from motor housing.
  • Page 46: V. Combustion-Air Blower

    V. COMBUSTION-AIR BLOWER 5. To remove motor, remove 4 screws that hold blower hous- ing to mounting plate. Remove the motor cooling fan by Clean periodically to assure proper airflow and heating effi- removing one setscrew. Remove nuts that hold motor to ciency.
  • Page 47: Condensate Drain Pan

    IX. CONDENSER COIL, EVAPORATOR COIL, AND After inspecting the electrical controls and wiring, replace all CONDENSATE DRAIN PAN the panels. Start the unit, and observe at least one complete heating cycle and one complete cooling cycle to ensure proper Inspect the condenser coil, evaporator coil, and condensate operation.
  • Page 48: Troubleshooting

    TROUBLESHOOTING Cooling SYMPTOM CAUSE REMEDY Compressor and Power failure Call power company. condenser fan will Fuse blown or circuit breaker tripped Replace fuse or reset circuit breaker. not start. Defective thermostat, contactor, transformer, Replace component. or control relay Insufficient line voltage Determine cause and correct.
  • Page 49 Cooling (cont) SYMPTOM CAUSE REMEDY Integrated control Blower wheel not secured to shaft Properly tighten blower wheel to shaft. motor Insufficient voltage at motor Determine cause and correct. (units 589A048,060 Power connectors not properly Connectors should snap easily; do not 208/230 v) seated force.
  • Page 50 Course descriptions and schedules are in our catalog. CALL FOR FREE CATALOG 1-800-962-9212 [ ] Packaged Service Training [ ] Classroom Service Training Copyright 1998 Bryant Heating & Cooling Systems CATALOG NO. CATALOG NO. 5358-802...
  • Page 52 IN. WG REFRIGERANT SUCTION PSIG REFRIGERANT DISCHARGE PSIG VERIFY REFRIGERANT CHARGE USING CHARGING TABLES VERIFY THAT 3-PHASE SCROLL COMPRESSOR (588A048,060 AND 589A036-060 UNITS) ROTATING IN CORRECT DIRECTION CL-1 Copyright 1998 Bryant Heating & Cooling Systems CATALOG NO. CATALOG NO. 5358-802...

This manual is also suitable for:

589a

Table of Contents

Save PDF