Notes on installation into the rack

V
CAUTION!
Because the system unit is heavy, at least three people are
needed to safely mount the BX900 S1 system unit in the rack.
(For the Japanese market, please refer to " 安全上のご注意 ").
Before lifting the system unit, remove all server blades, all power
supply units and the fan units to reduce the weight.
To lift or carry the system unit, always use the handles on the long
sides.
Never lift or carry the system unit by the handles on the front or back
of the unit.
For safety reasons, no more than one unit may be removed from the
rack at any one time during installation or maintenance work.
Make sure that the anti-tilt plate is correctly mounted when you set up
the rack.
The rack may tip over if more than one unit is removed at the same
time.
Before connecting or disconnecting cables, read the notes in the
chapter "Important Notes" in the technical manual for the relevant
rack. The technical manual for the rack is supplied with the rack.
The rack must be connected to the mains by an authorized specialist
(electrician).
If the server system is integrated in a rack installation that receives
power from an industrial (public) power supply network with the
IEC309 connector, the (public) power supply protection must comply
with the requirements for the non-industrial (public) power supply
networks for the type A connector.
The power supply for the rack should be distributed over the three
phases of a three-phase mains connection or over multiple power
sources.